SiME332106E
Troubleshooting by Error Code
Part 6 Service Diagnosis
155
5.2 Error Codes (Sub Codes)
If an error code like the one shown below is displayed when the navigation remote controller
(BRC1E series) is in use, make a detailed diagnosis or a diagnosis of the relevant unit referring
to the attached list of detailed error codes.
5.2.1 Indoor Unit
Error code
Troubleshooting
Description of error
Diagnosis
A6 - 01
Fan motor locked
A locked fan motor current has been detected.
Turn the fan by hand to check for the connection of connectors.
A6 - 10
Fan overcurrent error
A fan motor overcurrent has been detected.
Check for the connection of the connector between the fan motor and
the PCB for the fan. If the connection is normal, replace the fan motor. If
this still cannot solve the error, replace the PCB for the fan.
A6 - 11
Fan position detection error
An error in the detection of position of the fan motor. Check for the
connection of the connector between the fan motor and the PCB for the
fan. If the connection is normal, replace the fan motor. If this still cannot
solve the error, replace the PCB for the fan.
A8 - 01
Power supply voltage error
Check for the input voltage of the fan motor.
A9 - 01
Electronic expansion valve error
There is an error in the electronic expansion valve coil or a connector
disconnected.
A9 - 02
Refrigerant leakage detection error
Refrigerant leaks even if the electronic expansion valve is closed.
Replace the electronic expansion valve.
AH - 03
Transmission error (between the
self-cleaning decoration panel and the
indoor unit)
(when the self-cleaning decoration panel is
mounted)
Check for the connection of the harness connector between the panel
PCB and the indoor unit PCB.
AH - 04
Dust detection sensor error
(when the self-cleaning decoration panel is
mounted)
Check for the connections of the connector X12A on the panel PCB and
the connectors X18A and X19A on the sensor PCB.
AH - 05
Dust collection sign error
(when the self-cleaning decoration panel is
mounted)
Check for clogging with dust at the dust collection port as well as in the
brush unit, S-shaped pipe, and dust box. Furthermore, check for any
stains of the light receiving and emitting parts of the infrared unit.
AH - 06
Air filter rotation error
(when the self-cleaning decoration panel is
mounted)
Check for anything getting in the way of rotating the filter (e.g. the filter
comes off or the drive gear is clogged with foreign matter).
AH - 07
Damper rotation error
(when the self-cleaning decoration panel is
mounted)
The damper does not rotate normally. Check for any foreign matter
around the damper and for the operation of the gear and limit switch.
AH - 08
Filter self-cleaning operation error
(when the self-cleaning decoration panel is
mounted)
The unit has not yet completed the filter self-cleaning operation even
after the lapse of specified period of time. Check for any external noise,
etc.
AH - 09
Filter self-cleaning operation start disabled
error (when the self-cleaning decoration
panel is mounted)
The unit has been put into a state in which the filter self-cleaning
operation is disabled. Check the unit for the operating conditions.
AH - 12
Auto grille unit error
(when the auto grille unit is mounted)
It is detected that the grille does not operate properly. Check whether
the grille does not contact with something or the wire does not snaggle.
AJ - 01
Capacity setting error
There is an error in the capacity setting of the indoor unit PCB.
AJ - 02
Electronic expansion valve setting error
There is a fault in the setting of the gear type electronic expansion
valve/direct acting type electronic expansion valve.
C1 - 01
Transmission error (between indoor unit
PCB and the PCB for the fan)
Check for the conditions of transmission between the indoor unit PCB
and the PCB for the fan.
C1 - 06
Transmission error (between indoor unit
PCB and auto grille control PCB)
Refer to
C1-06
flowchart.
C6 - 01
Defective combination of indoor unit PCB
and the PCB for the fan
A combination of indoor unit PCB and the PCB for the fan is defective.
Check whether the capacity setting adaptor is correct and the type of
the PCB for the fan is correct.
C6 - 05
Indoor unit PCB abnormality
Refer to
C6-05
flowchart.
CE - 01
Infrared presence sensor error
The output of the infrared presence sensor is not detected.
Check if the connector is properly connected, and if the harness
is not broken
CE - 02
Infrared floor sensor error
A disconnection of the temperature correction circuit
(thermistor) of the infrared floor sensor has been detected.
Check if the connector is properly connected.
CE - 03
Infrared floor sensor error
A short-circuit of the temperature correction circuit (thermistor) of the
infrared floor sensor has been detected. Check if the pins of the
connector are touching each other, and if any foreign matter on the
PCB is causing a short-circuit.
Содержание VRV RXYMQ-A Series
Страница 1: ...Service Manual RXYMQ A Series Heat Pump 50 60 Hz SiME332106E...
Страница 283: ...SiME332106E Check Part 6 Service Diagnosis 277 PCB and Circuit Diagram U V W L3B L2B L1B P1 P2 N32...
Страница 296: ...SiME332106E 290 Part 7 Appendix 1 Wiring Diagrams 291 1 1 Outdoor Unit 291 1 2 VRV Indoor Unit 293 Part 7 Appendix...
Страница 297: ...SiME332106E Wiring Diagrams Part 7 Appendix 291 1 Wiring Diagrams 1 1 Outdoor Unit RXYMQ4AVMK C 3D133942...
Страница 298: ...Wiring Diagrams SiME332106E 292 Part 7 Appendix RXYMQ4 5 6AYFK C 3D133944A...
Страница 303: ...SiME332106E Wiring Diagrams Part 7 Appendix 297 FXMQ40 50 63 80 100ARV1 3D127112 04 59...