Troubleshooting by Error Code
SiME332106E
238
Part 6 Service Diagnosis
Note(s)
Reference
Troubleshooting
Subcode P4-01
Subcode P4-02
1. RXYMQ4AVMK: outdoor unit main PCB (A1P)
RXYMQ4-6AYFK: inverter PCB (A3P)
2. RXYMQ4AVMK: outdoor unit main PCB (A1P)
RXYMQ4-6AYFK: fan PCB (A4P)
CHECK 11
Refer to page 281.
Make measurement of
resistance of the radiation
fin thermistor.
The
insulation resistance
of the compressor is
less than 100 k
.
NO
YES
YES
NO
Replace the relevant PCB (
1
).
Replace the compressor
(M1C).
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
The insulation
resistance of the fan motor
is less than 1 M
.
Turn ON the
power supply.
Does the error
recur?
NO
YES
NO
YES
Replace the fan motor.
Replace the relevant PCB (
1
).
Continue operation.
CHECK 11
Is the resistance of the
radiation fin thermistor
normal?
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
NO
Replace the fan motor.
YES
The insulation
resistance of the fan
motor is
less than 1 M
.
Continue operation.
NO
Replace the relevant PCB
(
2
).
YES
Turn ON
the power supply.
Does the error recur?
Содержание VRV RXYMQ-A Series
Страница 1: ...Service Manual RXYMQ A Series Heat Pump 50 60 Hz SiME332106E...
Страница 283: ...SiME332106E Check Part 6 Service Diagnosis 277 PCB and Circuit Diagram U V W L3B L2B L1B P1 P2 N32...
Страница 296: ...SiME332106E 290 Part 7 Appendix 1 Wiring Diagrams 291 1 1 Outdoor Unit 291 1 2 VRV Indoor Unit 293 Part 7 Appendix...
Страница 297: ...SiME332106E Wiring Diagrams Part 7 Appendix 291 1 Wiring Diagrams 1 1 Outdoor Unit RXYMQ4AVMK C 3D133942...
Страница 298: ...Wiring Diagrams SiME332106E 292 Part 7 Appendix RXYMQ4 5 6AYFK C 3D133944A...
Страница 303: ...SiME332106E Wiring Diagrams Part 7 Appendix 297 FXMQ40 50 63 80 100ARV1 3D127112 04 59...