Troubleshooting by Error Code
SiME332106E
220
Part 6 Service Diagnosis
Reference
Troubleshooting
RXYMQ4AVMK
RXYMQ4-6AYFK
CHECK 4
Refer to page 275.
Replace the outdoor unit main
PCB (A1P).
YES
NO
It is supposed that the error results
from external causes other than
failures (e.g. exogenous noises or
thunder).
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Caution
Does the power
supply normally come
back on?
Turn off the power. Then,
turn on the power again.
Is the
insulation to
ground resistance of the
compressor 100 k
or
more?
The error could have resulted from
external factors other than failures
(e.g. external noise or thunder).
YES
Replace both the compressor (M1C)
and the inverter PCB (A3P).
Replace the inverter PCB (A3P).
NO
NO
YES
Replace both the inverter PCB (A3P)
and the fan PCB (A4P).
Replace the inverter PCB (A3P).
NO
YES
Turn off the power. Then,
turn on the power again.
NO
YES
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Return to normal?
CHECK 4
Is the power
transistor normal?
CHECK 4
Is the power
transistor of the fan
driver normal?
Содержание VRV RXYMQ-A Series
Страница 1: ...Service Manual RXYMQ A Series Heat Pump 50 60 Hz SiME332106E...
Страница 283: ...SiME332106E Check Part 6 Service Diagnosis 277 PCB and Circuit Diagram U V W L3B L2B L1B P1 P2 N32...
Страница 296: ...SiME332106E 290 Part 7 Appendix 1 Wiring Diagrams 291 1 1 Outdoor Unit 291 1 2 VRV Indoor Unit 293 Part 7 Appendix...
Страница 297: ...SiME332106E Wiring Diagrams Part 7 Appendix 291 1 Wiring Diagrams 1 1 Outdoor Unit RXYMQ4AVMK C 3D133942...
Страница 298: ...Wiring Diagrams SiME332106E 292 Part 7 Appendix RXYMQ4 5 6AYFK C 3D133944A...
Страница 303: ...SiME332106E Wiring Diagrams Part 7 Appendix 297 FXMQ40 50 63 80 100ARV1 3D127112 04 59...