Field Settings for Indoor Unit
SiME332106E
98
Part 5 Field Settings and Test Operation
1.4.12 Compensating the Temperature around People
Change the ratio between the suction air temperature and floor temperature used to calculate
the temperature around people.
The temperature around people is calculated using the values of the suction air thermistor and
the infrared floor sensor. The factory setting is "Normal" (the average value of the suction air
temperature and the floor temperature is applied). However, the rate at which the suction air
thermistor and the infrared floor sensor affect the temperature around people can be changed
with this setting.
To reflect the effect of the temperature around the ceiling, select the "Priorities given on the
suction air temperature" (the Second code No.
02
).
To reflect the effect of the temperature around the floor, select the "Priorities given on the
floor temperature" (the Second code No.
04
).
The infrared floor sensor can be disabled by selecting "Suction air temperature only" (the
Second code No.
01
).
: Factory setting
1.4.13 Compensating the Floor Temperature when Heating
Offset the detected value of the infrared floor sensor with a certain temperature. This setting
should be used to have the actual floor temperature detected when, for example, the unit is
installed close to a wall.
: Factory setting
Actual procedure to use the setting
Although the standard setting is normally used with no problem, the setting should be changed
in the following cases:
1.4.14 Optional Accessories Output Selection
Using this setting, "operation output signal" and "abnormal output signal" can be provided.
Output signal is output between terminals X1 and X2 of "adaptor for wiring", an optional
accessory.
: Factory setting
Mode
No.
First Code
No.
Second
Code No.
Contents
11 (21)
8
01
Suction air temperature only
02
Priority given on the suction air temperature
03
Standard
04
Priority given on the floor temperature
Mode
No.
First Code
No.
Second Code
No.
Contents
11 (21)
9
01
–4°C
02
–2°C
03
0°C
04
2°C
Environment
Operation
Mode
Problem
Setting Value
- The unit is installed close to a wall or a window.
- High thermal capacity of the floor (such as
concrete, etc.).
- There are many heat sources including PC.
- There is a non-negligible heat source such as
floor heating.
Heating
Excessive heating
2°C
Insufficient
heating
–2°C or –4°C
Mode
No.
First
Code No.
Second
Code No.
Contents
12 (22)
0
01
Indoor unit thermostat ON/OFF signal is provided
.
02
—
03
Output linked with ON/OFF of remote controller is provided.
04
In case of Error Display appears on the remote controller, output is
provided.
Содержание VRV RXYMQ-A Series
Страница 1: ...Service Manual RXYMQ A Series Heat Pump 50 60 Hz SiME332106E...
Страница 283: ...SiME332106E Check Part 6 Service Diagnosis 277 PCB and Circuit Diagram U V W L3B L2B L1B P1 P2 N32...
Страница 296: ...SiME332106E 290 Part 7 Appendix 1 Wiring Diagrams 291 1 1 Outdoor Unit 291 1 2 VRV Indoor Unit 293 Part 7 Appendix...
Страница 297: ...SiME332106E Wiring Diagrams Part 7 Appendix 291 1 Wiring Diagrams 1 1 Outdoor Unit RXYMQ4AVMK C 3D133942...
Страница 298: ...Wiring Diagrams SiME332106E 292 Part 7 Appendix RXYMQ4 5 6AYFK C 3D133944A...
Страница 303: ...SiME332106E Wiring Diagrams Part 7 Appendix 297 FXMQ40 50 63 80 100ARV1 3D127112 04 59...