Troubleshooting by Error Code
Part 6 Service Diagnosis
227
Note(s)
Reference
1. RXYMQ4AVMK: outdoor unit main PCB (A1P)
RXYMQ4-6AYFK: inverter PCB (A3P)
CHECK 4
Refer to page 275.
A
NO
YES
The
insulation
resistance of the
compressor is 100 k
or
less to ground.
Replace the compressor
(M1C).
YES
The internal
wiring of the
compressor coil is
defective.
Replace the compressor
(M1C).
YES
NO
Replace the relevant
PCB
(
1)
.
NO
Power OFF
CHECK 4
Is the power
transistor normal?
YES
The difference
between high and low pressure
before restarting is less than
0.2 MPa.
Defective equalization of
the refrigerant line.
NO
YES
L8
recurs.
Continue operation.
NO
Connect the compressor lead
wires and restart.
Power OFF
YES
Restarting the
system results in the
recurrence of the
error.
Continue operation.
NO
Replace the inverter PCB (A3P).
RXYMQ4-6AYFK Only
Diagnose the
compressor (M1C).
Содержание VRV RXYMQ-A Series
Страница 1: ...Service Manual RXYMQ A Series Heat Pump 50 60 Hz SiME332106E...
Страница 283: ...SiME332106E Check Part 6 Service Diagnosis 277 PCB and Circuit Diagram U V W L3B L2B L1B P1 P2 N32...
Страница 296: ...SiME332106E 290 Part 7 Appendix 1 Wiring Diagrams 291 1 1 Outdoor Unit 291 1 2 VRV Indoor Unit 293 Part 7 Appendix...
Страница 297: ...SiME332106E Wiring Diagrams Part 7 Appendix 291 1 Wiring Diagrams 1 1 Outdoor Unit RXYMQ4AVMK C 3D133942...
Страница 298: ...Wiring Diagrams SiME332106E 292 Part 7 Appendix RXYMQ4 5 6AYFK C 3D133944A...
Страница 303: ...SiME332106E Wiring Diagrams Part 7 Appendix 297 FXMQ40 50 63 80 100ARV1 3D127112 04 59...