SiME332106E
Field Settings for Indoor Unit
Part 5 Field Settings and Test Operation
95
1.4.3 Filter Cleaning Sign
Whether or not to display the sign after operation of a certain duration can be selected.
: Factory setting
1.4.4 Information for intelligent Touch Manager / intelligent Touch
Controller
: Factory setting
When field setting 10 (20)-6-
02
is set at the same time as 10 (20)-2-
01,02,03,
field setting 10
(20)-2 has priority. When field setting 10 (20)-6-
01
is set at the same time as 10
(20)-2-
01,02,03,
field setting 10 (20)-6 has priority for group connection, and 10 (20)-2 has
priority for individual connection.
1.4.5 Time for Absence Area Detection
By selecting the energy-saving operation mode when absent, the target temperature is shifted
to the energy-saving end by 1°C (maximum 2°C) after the state of absence continues for a
certain period of time.
Absent time defined for detection can be selected as follows:
: Factory setting
The set temperature displayed on the remote controller remains the same even if the target
temperature is shifted.
As soon as people are detected while the temperature is shifted, this control will be
cancelled (reset).
Mode
No.
First Code
No.
Second
Code No.
Contents
10 (20)
3
01
Displayed
02
Not displayed
Mode
No.
First Code
No.
Second
Code No.
Contents
10 (20)
5
01
Only indoor unit sensor value (or remote controller sensor
value, if installed.)
02
Sensor values according to 10 (20)-2 and 10 (20)-6.
Mode
No.
First Code No. Second Code
No.
Contents
10 (20)
7
01
30 minutes
02
60 minutes
30 (60)
∗
60 (120)
∗
31
19
28
27
26
17
21
30
29
20
18
Elapsed time of absence (min.)
Set temperature (°C)
Human detection
Cooling (at 28°C)
Heating (at 20°C)
State of absence
∗
The values in parentheses represent the time
when Second code No. is
02
.
Содержание VRV RXYMQ-A Series
Страница 1: ...Service Manual RXYMQ A Series Heat Pump 50 60 Hz SiME332106E...
Страница 283: ...SiME332106E Check Part 6 Service Diagnosis 277 PCB and Circuit Diagram U V W L3B L2B L1B P1 P2 N32...
Страница 296: ...SiME332106E 290 Part 7 Appendix 1 Wiring Diagrams 291 1 1 Outdoor Unit 291 1 2 VRV Indoor Unit 293 Part 7 Appendix...
Страница 297: ...SiME332106E Wiring Diagrams Part 7 Appendix 291 1 Wiring Diagrams 1 1 Outdoor Unit RXYMQ4AVMK C 3D133942...
Страница 298: ...Wiring Diagrams SiME332106E 292 Part 7 Appendix RXYMQ4 5 6AYFK C 3D133944A...
Страница 303: ...SiME332106E Wiring Diagrams Part 7 Appendix 297 FXMQ40 50 63 80 100ARV1 3D127112 04 59...