SiME332106E
Troubleshooting by Error Code
Part 6 Service Diagnosis
187
5.19 Indoor Unit PCB Abnormality
Applicable
Models
FXFSQ-AR
Error Code
C6-05
Method of Error
Detection
This error is detected by checking the current sensor value.
Error Decision
Conditions
When an abnormal signal is detected at the start of operation of the fan motor.
Supposed
Causes
Disconnection of the connector of the fan motor lead wire
Defective fan motor (Broken wires or defective insulation)
Defective PCB (A1P)
Troubleshooting
Replace the fan motor.
Resistances
between UVW phases of
the fan motor are imbalanced, or
there is a short circuit
between UVW.
Is the fan
motor connector (X901A)
connected properly?
YES
Properly connect the connector.
Replace the indoor unit PCB
(A1P).
NO
YES
NO
Turn OFF the power supply, and then
wait for a period of 10 minutes.
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Содержание VRV RXYMQ-A Series
Страница 1: ...Service Manual RXYMQ A Series Heat Pump 50 60 Hz SiME332106E...
Страница 283: ...SiME332106E Check Part 6 Service Diagnosis 277 PCB and Circuit Diagram U V W L3B L2B L1B P1 P2 N32...
Страница 296: ...SiME332106E 290 Part 7 Appendix 1 Wiring Diagrams 291 1 1 Outdoor Unit 291 1 2 VRV Indoor Unit 293 Part 7 Appendix...
Страница 297: ...SiME332106E Wiring Diagrams Part 7 Appendix 291 1 Wiring Diagrams 1 1 Outdoor Unit RXYMQ4AVMK C 3D133942...
Страница 298: ...Wiring Diagrams SiME332106E 292 Part 7 Appendix RXYMQ4 5 6AYFK C 3D133944A...
Страница 303: ...SiME332106E Wiring Diagrams Part 7 Appendix 297 FXMQ40 50 63 80 100ARV1 3D127112 04 59...