SiME332106E
Field Settings for Outdoor Unit
Part 5 Field Settings and Test Operation
129
Default value: 1. RA cool/heat master logic. Any RA indoor unit that is switched first, is
assigned as cool/heat master as long this unit is in operation (regardless thermostat
status). Only when this indoor unit is switched OFF operation (by remote controller),
other indoor unit can become cool/heat master:
Priority is given to indoor unit operating in the same mode as the previous cool/heat
master switched OFF operation.
Only no more indoor unit operate in the same mode as the previous cool/heat master,
other RA indoor unit can become cool/heat master to switch to the other operation
mode.
RA indoor unit that is operating, but demanding the other operation mode set by the
cool/heat master, enters the “stand-by mode”: operation LED blinks.
VRV
indoor unit change the operation mode immediately when outdoor unit receives
change of operation mode from the current cool/heat master RA indoor unit.
Field Setting 0:
VRV
cool/heat master logic.
At time of first startup, or when cool/heat master was released, one of connected
VRV
DX indoor unit can be assigned cool/heat master. The symbol “locked cool/heat
selector”
blinks. In case of wireless controller kit is used, the green clock LED
blinks on the receiver.
Confirm cool/heat master to a
VRV
DX indoor unit: press once the cool/heat selector
button
on the remote controller of the indoor unit to be set as cool/heat master.
Mode 2-84:
Initial opening electronic expansion valve BP
unit heating thermostat-ON:
Default value: 1 (500 pulse)
Field setting 0: 400 pulse, 2: 600 pulse, 3: 300 pulse.
Mode 2-90:
Indoor unit without power U4
error generation. In case an indoor unit needs
maintenance or repair on the electric side, it is possible to keep the rest of the
VRV
DX
indoor units operating without power supply to some indoor unit(s).
Default value: 0. Not active.
Field setting 1: Possible to operate system when some indoor units are temporary
without power supply. The following conditions must be fulfilled:
Maximum equivalent piping length of the farthest indoor less than 120 m.
Index indoor units power simultaneously less than 30% of the nominal outdoor.
Total capacity is less than 30% of the nominal one of the outdoor unit.
Operation time is limited to 24 hours period.
It is recommended to shut down connected indoor units at the same floor.
Not possible to use service mode operation (e.g. recovery mode).
Backup operation has priority over this special feature.
Not possible to use when the indoor unit electronic expansion valve is defective.
Not possible to use with systems that include BP units.
It is necessary to wait for 10 min. before shutting down the connected indoor units
after indoor units operation is stopped.
Mode 2-96:
Eco level setting for Eco mode by main PCB
Default value: 0
Mode 2-96
Eco level setting
0
OFF (default)
1
Low
2
Standard
Содержание VRV RXYMQ-A Series
Страница 1: ...Service Manual RXYMQ A Series Heat Pump 50 60 Hz SiME332106E...
Страница 283: ...SiME332106E Check Part 6 Service Diagnosis 277 PCB and Circuit Diagram U V W L3B L2B L1B P1 P2 N32...
Страница 296: ...SiME332106E 290 Part 7 Appendix 1 Wiring Diagrams 291 1 1 Outdoor Unit 291 1 2 VRV Indoor Unit 293 Part 7 Appendix...
Страница 297: ...SiME332106E Wiring Diagrams Part 7 Appendix 291 1 Wiring Diagrams 1 1 Outdoor Unit RXYMQ4AVMK C 3D133942...
Страница 298: ...Wiring Diagrams SiME332106E 292 Part 7 Appendix RXYMQ4 5 6AYFK C 3D133944A...
Страница 303: ...SiME332106E Wiring Diagrams Part 7 Appendix 297 FXMQ40 50 63 80 100ARV1 3D127112 04 59...