Special Control
SiME332106E
66
Part 4 Functions and Control
7.2.2 Oil Return Control in Heating Operation
Part Name
Electric
Symbol
RXYMQ-A
Function
Compressor motor
M1C
RXYMQ4AVMK: 70 rps
RXYMQ4-6AYFK: 79 rps
Fan motor
M1F
With high pressure
OFF ←→ Step 4 ←→ Step 6
Electronic expansion valve
(Main)
Y1E
480 pulses
Electronic expansion valve
(Injection)
Y2E
0 pulse
Electronic expansion valve
(Refrigerant jacket)
Y3E
480 pulse
(0-480 pulse, when radiation fin temperature
increases)
Electronic expansion valve
(Refrigerant auto charge)
Y4E
480 pulse
Four way valve
Y1S
OFF
Ending conditions
• A lapse of 6 min.
• Ts–Te < 3°C
OR
Indoor unit actuator
Heating oil return control
Fan
Thermostat ON unit
OFF
Stopping unit
OFF
Thermostat OFF unit
OFF
Electronic expansion valve
Thermostat ON unit
Oil return EV opening degree
Stopping unit
Oil return EV opening degree
Thermostat OFF unit
Oil return EV opening degree
Содержание VRV RXYMQ-A Series
Страница 1: ...Service Manual RXYMQ A Series Heat Pump 50 60 Hz SiME332106E...
Страница 283: ...SiME332106E Check Part 6 Service Diagnosis 277 PCB and Circuit Diagram U V W L3B L2B L1B P1 P2 N32...
Страница 296: ...SiME332106E 290 Part 7 Appendix 1 Wiring Diagrams 291 1 1 Outdoor Unit 291 1 2 VRV Indoor Unit 293 Part 7 Appendix...
Страница 297: ...SiME332106E Wiring Diagrams Part 7 Appendix 291 1 Wiring Diagrams 1 1 Outdoor Unit RXYMQ4AVMK C 3D133942...
Страница 298: ...Wiring Diagrams SiME332106E 292 Part 7 Appendix RXYMQ4 5 6AYFK C 3D133944A...
Страница 303: ...SiME332106E Wiring Diagrams Part 7 Appendix 297 FXMQ40 50 63 80 100ARV1 3D127112 04 59...