Troubleshooting by Error Code
SiME332106E
166
Part 6 Service Diagnosis
Reference
5.7 Indoor Fan Motor Abnormality
5.7.1 Indoor Fan Motor Abnormality (FXDQ-PD, FXDQ-ND)
Applicable
Models
FXDQ-PD, FXDQ-ND
Error Code
A6
Method of Error
Detection
This error is detected if there is no revolution detection signal output from the fan motor.
Error Decision
Conditions
When no revolutions can be detected even at the maximum output voltage to the fan
Supposed
Causes
Defective indoor fan motor
Broken wires
Defective contact
Troubleshooting
CHECK 16
Refer to page 285.
YES
NO
NO
YES
Check the indoor fan motor and
the wiring circuits of the fan
motor.
Replace the indoor unit control
PCB (A1P).
Properly connect the connectors.
(At this time, check for any
defective connector contact or
broken wires.)
Are the
X4A and X27A
connectors securely
connected?
Is
the
power of 12
VDC supplied
between the Pins 1
and 3 when the X27A is
disconnected and the
power supply turns
ON?
CHECK 16
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Содержание VRV RXYMQ-A Series
Страница 1: ...Service Manual RXYMQ A Series Heat Pump 50 60 Hz SiME332106E...
Страница 283: ...SiME332106E Check Part 6 Service Diagnosis 277 PCB and Circuit Diagram U V W L3B L2B L1B P1 P2 N32...
Страница 296: ...SiME332106E 290 Part 7 Appendix 1 Wiring Diagrams 291 1 1 Outdoor Unit 291 1 2 VRV Indoor Unit 293 Part 7 Appendix...
Страница 297: ...SiME332106E Wiring Diagrams Part 7 Appendix 291 1 Wiring Diagrams 1 1 Outdoor Unit RXYMQ4AVMK C 3D133942...
Страница 298: ...Wiring Diagrams SiME332106E 292 Part 7 Appendix RXYMQ4 5 6AYFK C 3D133944A...
Страница 303: ...SiME332106E Wiring Diagrams Part 7 Appendix 297 FXMQ40 50 63 80 100ARV1 3D127112 04 59...