Check
SiME332106E
274
Part 6 Service Diagnosis
Reference
Reference
CHECK 7
Refer to page 279.
CHECK 8
Refer to page 280.
4. Judgment criteria of superheat operation:
(1) Suction gas superheating degree: 10°C and over.
(2) Discharge gas superheating degree: 45°C and over, except immediately after
compressor starts up or is running under dropping control.
(Use the above values as a guide. Depending on the other conditions, the unit may
be normal despite the values within the above range.)