Troubleshooting by Error Code
SiME332106E
224
Part 6 Service Diagnosis
5.42 Compressor Instantaneous Overcurrent
Applicable
Models
All outdoor unit models
Error Code
L5
Method of Error
Detection
Detect current flowing through the power transistor.
Error Decision
Conditions
The current instantaneously exceeds
A
(A) in the power transistor.
Trigger point
Supposed
Causes
Defective compressor coil (such as wiring disconnection or insulation failure)
Compressor startup failure (mechanical lock)
Defective outdoor unit main PCB (RXYMQ4AVMK)
Defective inverter PCB (RXYMQ4-6AYFK)
Troubleshooting
Compressor model
A
(A)
2Y350APAX2N
48.1
2Y420AVAY1N
48.55
Power OFF
Open the stop valve.
YES
NO
Is the stop valve open?
YES
YES
Are
wiring and wire
connections to the
compressor
normal?
Rectify the wiring and
wire connections.
NO
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Check for the leads of the
compressor.
• For compressor M1C
Are the
leads of the
compressor normal?
Replace the leads of the
compressor.
NO
A
Содержание VRV RXYMQ-A Series
Страница 1: ...Service Manual RXYMQ A Series Heat Pump 50 60 Hz SiME332106E...
Страница 283: ...SiME332106E Check Part 6 Service Diagnosis 277 PCB and Circuit Diagram U V W L3B L2B L1B P1 P2 N32...
Страница 296: ...SiME332106E 290 Part 7 Appendix 1 Wiring Diagrams 291 1 1 Outdoor Unit 291 1 2 VRV Indoor Unit 293 Part 7 Appendix...
Страница 297: ...SiME332106E Wiring Diagrams Part 7 Appendix 291 1 Wiring Diagrams 1 1 Outdoor Unit RXYMQ4AVMK C 3D133942...
Страница 298: ...Wiring Diagrams SiME332106E 292 Part 7 Appendix RXYMQ4 5 6AYFK C 3D133944A...
Страница 303: ...SiME332106E Wiring Diagrams Part 7 Appendix 297 FXMQ40 50 63 80 100ARV1 3D127112 04 59...