SiME332106E
Troubleshooting by Error Code
Part 6 Service Diagnosis
203
Troubleshooting
There is
foreign matter around the
applicable fan.
Remove the foreign matter.
YES
Check for the connections of fan motor connector.
NO
Turn OFF the power supply, and then wait for a period of 10 minutes.
Connector is
disconnected.
Insert the connector.
YES
NO
NO
Replace the relevant PCB
(
2).
YES
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
A
Check for Connection of Connector
The fan
can be rotated
by hand when
disconnecting the
connector from the
fan motor.
Replace the fan motor (M1F).
NO
Resistance
between the fan
motor power supply cable
terminal and the motor frame
(metallic part) is less
than 1 M
.
Replace the fan motor (M1F).
YES
YES
NO
The fuse
(
1)
on the
relevant PCB
(
2) has
continuity.
Содержание VRV RXYMQ-A Series
Страница 1: ...Service Manual RXYMQ A Series Heat Pump 50 60 Hz SiME332106E...
Страница 283: ...SiME332106E Check Part 6 Service Diagnosis 277 PCB and Circuit Diagram U V W L3B L2B L1B P1 P2 N32...
Страница 296: ...SiME332106E 290 Part 7 Appendix 1 Wiring Diagrams 291 1 1 Outdoor Unit 291 1 2 VRV Indoor Unit 293 Part 7 Appendix...
Страница 297: ...SiME332106E Wiring Diagrams Part 7 Appendix 291 1 Wiring Diagrams 1 1 Outdoor Unit RXYMQ4AVMK C 3D133942...
Страница 298: ...Wiring Diagrams SiME332106E 292 Part 7 Appendix RXYMQ4 5 6AYFK C 3D133944A...
Страница 303: ...SiME332106E Wiring Diagrams Part 7 Appendix 297 FXMQ40 50 63 80 100ARV1 3D127112 04 59...