Troubleshooting by Error Code
SiME332106E
168
Part 6 Service Diagnosis
Troubleshooting
YES
YES
The fan
motor connectors
(X1A and X2A) of the fan PCB
(A2P) are disconnected.
YES
NO
Remove the foreign matter.
NO
YES
NO
NO
YES
NO
NO
YES
Remove the power wire
connector from the fan motor
and measure the resistance
between U and V, V and W, and
W and U phases.
Replace the fan PCB (A2P).
Turn off the power and wait for
10 minutes.
There is a
foreign matter around the
fan.
Connect the connector
properly.
Replace the indoor fan
motor (M1F).
Replace the indoor fan
motor (M1F).
Connect the connector
properly.
CHECK 16
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
A
The connectors
between the indoor unit
PCB (A1P) and the fan
PCB (A2P) are
disconnected.
The fuse (F3U, white)
on the fan PCB (A2P)
has continuity.
The fan
can be moved lightly
by hand after the fan motor
connector of the fan PCB
(A2P) is removed.
The
resistance between
the power wire terminals of
the fan motor and motor frame
(metal part) is 1 M
or
below.
Go to the next page.
Содержание VRV RXYMQ-A Series
Страница 1: ...Service Manual RXYMQ A Series Heat Pump 50 60 Hz SiME332106E...
Страница 283: ...SiME332106E Check Part 6 Service Diagnosis 277 PCB and Circuit Diagram U V W L3B L2B L1B P1 P2 N32...
Страница 296: ...SiME332106E 290 Part 7 Appendix 1 Wiring Diagrams 291 1 1 Outdoor Unit 291 1 2 VRV Indoor Unit 293 Part 7 Appendix...
Страница 297: ...SiME332106E Wiring Diagrams Part 7 Appendix 291 1 Wiring Diagrams 1 1 Outdoor Unit RXYMQ4AVMK C 3D133942...
Страница 298: ...Wiring Diagrams SiME332106E 292 Part 7 Appendix RXYMQ4 5 6AYFK C 3D133944A...
Страница 303: ...SiME332106E Wiring Diagrams Part 7 Appendix 297 FXMQ40 50 63 80 100ARV1 3D127112 04 59...