Troubleshooting by Error Code
SiME332106E
254
Part 6 Service Diagnosis
Indication
after launch test
operation?
U4-03
The PCBs of indoor units
displaying
U9
are normal.
Check for indoor units of
other systems to troubleshoot
them according to relevant
error codes.
NO
YES
Check controller indoor units:
(1) Some error about
thermistor, or fan motor,
electronic expansion
valve, or defective PCB.
(2) Test operation was
interrupted by the
MODE
(BS1)
button.
YES
Check all indoor error
indication.
NO
Operate all indoor units.
YES
Do all units display
U9
?
Carry out the diagnosis again
after a lapse of 2 minutes or
more.
NO
Did 2 minutes or more
elapse after
U9
is
displayed?
Содержание VRV RXYMQ-A Series
Страница 1: ...Service Manual RXYMQ A Series Heat Pump 50 60 Hz SiME332106E...
Страница 283: ...SiME332106E Check Part 6 Service Diagnosis 277 PCB and Circuit Diagram U V W L3B L2B L1B P1 P2 N32...
Страница 296: ...SiME332106E 290 Part 7 Appendix 1 Wiring Diagrams 291 1 1 Outdoor Unit 291 1 2 VRV Indoor Unit 293 Part 7 Appendix...
Страница 297: ...SiME332106E Wiring Diagrams Part 7 Appendix 291 1 Wiring Diagrams 1 1 Outdoor Unit RXYMQ4AVMK C 3D133942...
Страница 298: ...Wiring Diagrams SiME332106E 292 Part 7 Appendix RXYMQ4 5 6AYFK C 3D133944A...
Страница 303: ...SiME332106E Wiring Diagrams Part 7 Appendix 297 FXMQ40 50 63 80 100ARV1 3D127112 04 59...