Check
SiME332106E
276
Part 6 Service Diagnosis
RXYMQ4-6AYFK
Perform the following procedures prior to check.
(1) Power OFF.
(2) Remove all the wiring connected to the PCB where power transistors are mounted on.
Point of Measurement and Judgment Criteria
Turn OFF the power supply. Then, after a lapse of 10 minutes or more, make measurement of
resistance.
When using the analog type of multimeter,
make measurement in resistance measurement mode in the x1 k
range.
When using the digital type of multimeter, make measurement in diode check mode.
Preparation
Multimeter
Prepare the analog type of multimeter.
For the digital type of multimeter, those with
diode check function are available for the
checking.
No.
Measuring point
Judgment
Criteria
Remarks
+
–
1
P2
U
2 ~ 15 k
―
2
P2
V
3
P2
W
4
U
P2
15 k
and
more
(including ∞ )
Due to
condenser
charge and so
on, resistance
measurement
may require
some time.
5
V
P2
6
W
P2
7
N32
U
8
N32
V
9
N32
W
10
U
N32
2 ~ 15 k
―
11
V
N32
12
W
N32
No.
Measuring point
Judgment
Criteria
Remarks
+
–
1
P2
U
1.2 V and more
Due to
condenser
charge and so
on, resistance
measurement
may require
some time.
2
P2
V
3
P2
W
4
U
P2
0.3 ~ 0.7 V
―
5
V
P2
6
W
P2
7
N32
U
8
N32
V
9
N32
W
10
U
N32
1.2 V and more
Due to
condenser
charge and so
on, resistance
measurement
may require
some time.
11
V
N32
12
W
N32
Содержание VRV RXYMQ-A Series
Страница 1: ...Service Manual RXYMQ A Series Heat Pump 50 60 Hz SiME332106E...
Страница 283: ...SiME332106E Check Part 6 Service Diagnosis 277 PCB and Circuit Diagram U V W L3B L2B L1B P1 P2 N32...
Страница 296: ...SiME332106E 290 Part 7 Appendix 1 Wiring Diagrams 291 1 1 Outdoor Unit 291 1 2 VRV Indoor Unit 293 Part 7 Appendix...
Страница 297: ...SiME332106E Wiring Diagrams Part 7 Appendix 291 1 Wiring Diagrams 1 1 Outdoor Unit RXYMQ4AVMK C 3D133942...
Страница 298: ...Wiring Diagrams SiME332106E 292 Part 7 Appendix RXYMQ4 5 6AYFK C 3D133944A...
Страница 303: ...SiME332106E Wiring Diagrams Part 7 Appendix 297 FXMQ40 50 63 80 100ARV1 3D127112 04 59...