SiME332106E
Outline of Control (Indoor Unit)
Part 4 Functions and Control
77
Note(s)
8.8 Freeze-Up Prevention Control
Freeze-Up Prevention by Off Cycle (Indoor Unit Individual Control)
When the temperature detected by liquid pipe temperature thermistor of the indoor heat
exchanger drops too low, the unit enters freeze-up prevention control in accordance with the
following conditions, and is also set in accordance with the conditions given below. (Thermostat
OFF)
When freeze-up prevention is activated, the airflow rate is fixed to L tap. When the following
conditions for cancelling are satisfied, it will reset.
Conditions for starting:
Liquid pipe temperature ≤ – 1°C (for total of 40 minutes)
or
Liquid pipe temperature ≤ – 5°C (for total of 10 minutes)
Condition for cancelling:
Liquid pipe temperature ≥ +7°C (for 10 minutes continuously)
Concept of freeze-up prevention control
System avoids freeze-up
For comfort, system avoids unnecessary thermostat ON/OFF
For ensuring compressor reliability, system avoids unnecessary compressor ON/OFF
When freeze-up prevention control starts, system makes sure the frost is completely removed.
System avoids water leakage.
When the indoor unit is a round flow or multi flow type, if the air outlet is set as dual-directional
or tri-directional, the starting conditions will be changed as follows.
Liquid pipe temperature
1°C (for total of 15 minutes)
or
Liquid pipe temperature
0°C (for 1 minute continuously)
During freeze-up prevention control, the airflow rate is fixed to LL.
(The cancelling conditions are same as the standard.)
Normal operation
Start
Cancel
Liquid pipe
temperature
–5ºC
0ºC
+7ºC
10 min.
10 min.
Freeze-up prevention control
Forced OFF by thermostat
Содержание VRV RXYMQ-A Series
Страница 1: ...Service Manual RXYMQ A Series Heat Pump 50 60 Hz SiME332106E...
Страница 283: ...SiME332106E Check Part 6 Service Diagnosis 277 PCB and Circuit Diagram U V W L3B L2B L1B P1 P2 N32...
Страница 296: ...SiME332106E 290 Part 7 Appendix 1 Wiring Diagrams 291 1 1 Outdoor Unit 291 1 2 VRV Indoor Unit 293 Part 7 Appendix...
Страница 297: ...SiME332106E Wiring Diagrams Part 7 Appendix 291 1 Wiring Diagrams 1 1 Outdoor Unit RXYMQ4AVMK C 3D133942...
Страница 298: ...Wiring Diagrams SiME332106E 292 Part 7 Appendix RXYMQ4 5 6AYFK C 3D133944A...
Страница 303: ...SiME332106E Wiring Diagrams Part 7 Appendix 297 FXMQ40 50 63 80 100ARV1 3D127112 04 59...