Field Settings for Outdoor Unit
SiME332106E
112
Part 5 Field Settings and Test Operation
2.3 Settings by BS Buttons
The following settings can be made using the BS buttons on the PCB.
Normal mode:
Blank: If no abnormality is detected and initialization of communication was completed.
Flashing combination of letter and number (4 digits): Error code detected by outdoor
control or trouble by communication.
Setting mode: Used to make changes to operating status, performance settings or address
setting.
Monitor mode: Used to verify contents of settings, quantity of units, current value of some
parameters during operation of outdoor unit.
Mode changing procedure can be selected using the MODE (BS1) button as shown
below:
MODE
BS1
SET
(TEST)
BS2
RETURN
(RESET)
BS3
Used to make
setting mode
changes.
Used to make
field settings.
7 segment display (SEG1-3)
BS buttons
Normal mode
Setting mode
Monitor mode
SEG1 SEG2 SEG3
Monitor mode
Press the
MODE
(BS1)
button once
Setting mode
Press and hold the
MODE (BS1)
button
for 5 seconds or more
Press the
MODE
(BS1)
button once
SEG1 SEG2 SEG3
SEG1 SEG2 SEG3
SEG1 SEG2 SEG3
Normal mode
Содержание VRV RXYMQ-A Series
Страница 1: ...Service Manual RXYMQ A Series Heat Pump 50 60 Hz SiME332106E...
Страница 283: ...SiME332106E Check Part 6 Service Diagnosis 277 PCB and Circuit Diagram U V W L3B L2B L1B P1 P2 N32...
Страница 296: ...SiME332106E 290 Part 7 Appendix 1 Wiring Diagrams 291 1 1 Outdoor Unit 291 1 2 VRV Indoor Unit 293 Part 7 Appendix...
Страница 297: ...SiME332106E Wiring Diagrams Part 7 Appendix 291 1 Wiring Diagrams 1 1 Outdoor Unit RXYMQ4AVMK C 3D133942...
Страница 298: ...Wiring Diagrams SiME332106E 292 Part 7 Appendix RXYMQ4 5 6AYFK C 3D133944A...
Страница 303: ...SiME332106E Wiring Diagrams Part 7 Appendix 297 FXMQ40 50 63 80 100ARV1 3D127112 04 59...