Troubleshooting by Error Code
SiME332106E
156
Part 6 Service Diagnosis
As there are various combinations of indoor and outdoor units, the sub codes of A0 - A3 are not
shown in this table.
CE - 04
Infrared floor sensor error
An abnormality other than the ones mentioned above has been
detected.
Check if the temperature nearby the sensor is too high, and if there is
any foreign matter that may cause noise.
U4 - 01
Indoor-Outdoor transmission error
Refer to the
U4
flowchart.
UA - 13
Refrigerant type error
The type of refrigerant used for the indoor unit is different from that
used for the outdoor unit.
UA - 15
Not applicable for self-cleaning decoration
panel (when the self-cleaning decoration
panel is mounted)
An outdoor unit is not applicable for the self-cleaning decoration panel
is connected.
Error code
Troubleshooting
Description of error
Diagnosis