Troubleshooting by Error Code
SiME332106E
200
Part 6 Service Diagnosis
5.27 Compressor Motor Lock
Applicable
Models
All outdoor unit models
Error Code
E5
Method of Error
Detection
Outdoor unit main PCB takes the position signal from UVW line connected between the inverter
and compressor, and the error is detected when any abnormality is observed in the
phase-current waveform.
Error Decision
Conditions
When the compressor motor does not operate even by starting it in forced startup mode.
Supposed
Causes
Compressor lock
High differential pressure (0.5 MPa or more)
UVW connection error
Defective inverter circuit
The stop valve is not opened.
Troubleshooting
Make proper wire connections.
Make proper wire connections.
NO
NO
NO
NO
YES
YES
YES
YES
Power OFF
Is the
connection line
of the compressor
normal?
Are wire
connections
made to phases U, V
and W in the proper
order and
manner?
Are wire
connections
made according
to the wiring
diagram?
Is the stop
valve open?
Replace the connection line,
and then securely connect the
connector.
Field factor
Open the stop valve.
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
A
Check the connection wiring for
compressor M1C.
U
V
W
Содержание VRV RXYMQ-A Series
Страница 1: ...Service Manual RXYMQ A Series Heat Pump 50 60 Hz SiME332106E...
Страница 283: ...SiME332106E Check Part 6 Service Diagnosis 277 PCB and Circuit Diagram U V W L3B L2B L1B P1 P2 N32...
Страница 296: ...SiME332106E 290 Part 7 Appendix 1 Wiring Diagrams 291 1 1 Outdoor Unit 291 1 2 VRV Indoor Unit 293 Part 7 Appendix...
Страница 297: ...SiME332106E Wiring Diagrams Part 7 Appendix 291 1 Wiring Diagrams 1 1 Outdoor Unit RXYMQ4AVMK C 3D133942...
Страница 298: ...Wiring Diagrams SiME332106E 292 Part 7 Appendix RXYMQ4 5 6AYFK C 3D133944A...
Страница 303: ...SiME332106E Wiring Diagrams Part 7 Appendix 297 FXMQ40 50 63 80 100ARV1 3D127112 04 59...