Troubleshooting by Error Code
SiME332106E
268
Part 6 Service Diagnosis
Reference
CHECK 15
Refer to page 285.
Check the
transmission
wiring between main
centralized controller for
any broken wire.
Check
the transmission
wiring between
centralized controller for
any broken wire.
Is the
voltage
between the
terminals F1 (+) and F2 (-)
in the range of 15.2
to 17.6 VDC?
Replace the centralized
controller.
Centralized controller:
Normal
OK
Correct the wiring.
NG
A
NO
Correct the wiring.
NG
YES
YES
Disconnect the transmission
wiring of the main centralized
controller, and then check the
voltage between the
transmission terminals (F1 and
F2) of the master unit
transmission equipment using
a multimeter.
It is supposed that the error
results from external factors
(e.g. noises) from other
equipment.
CHECK 15
Has the main
centralized controller setting
connector been
connected?
OK
Correct the connection of the
connector.
NO
CHECK 15
Содержание VRV RXYMQ-A Series
Страница 1: ...Service Manual RXYMQ A Series Heat Pump 50 60 Hz SiME332106E...
Страница 283: ...SiME332106E Check Part 6 Service Diagnosis 277 PCB and Circuit Diagram U V W L3B L2B L1B P1 P2 N32...
Страница 296: ...SiME332106E 290 Part 7 Appendix 1 Wiring Diagrams 291 1 1 Outdoor Unit 291 1 2 VRV Indoor Unit 293 Part 7 Appendix...
Страница 297: ...SiME332106E Wiring Diagrams Part 7 Appendix 291 1 Wiring Diagrams 1 1 Outdoor Unit RXYMQ4AVMK C 3D133942...
Страница 298: ...Wiring Diagrams SiME332106E 292 Part 7 Appendix RXYMQ4 5 6AYFK C 3D133944A...
Страница 303: ...SiME332106E Wiring Diagrams Part 7 Appendix 297 FXMQ40 50 63 80 100ARV1 3D127112 04 59...