SiME332106E
Servicing Items to be Confirmed
Part 6 Service Diagnosis
143
minute before entering service mode again. In case of continuous execution, the outdoor unit
PCB may sometimes display an error code. If any error codes are displayed, press the
RETURN (BS3)
button. If performing the above operation still does not eliminate the error,
reconnect the unit to the power supply.
1.3 Refrigerant Properties (R-410A)
Temperature
(°C)
Absolute
Pressure
(MPa)
Temperature
(°C)
Absolute
Pressure
(MPa)
Temperature
(°C)
Absolute
Pressure
(MPa)
Temperature
(°C)
Absolute
Pressure
(MPa)
–50
0.11
–20
0.40
10
1.09
40
2.42
–48
0.12
–18
0.43
12
1.15
42
2.54
–46
0.13
–16
0.46
14
1.22
44
2.67
–44
0.15
–14
0.50
16
1.29
46
2.80
–42
0.16
–12
0.54
18
1.37
48
2.93
–40
0.18
–10
0.57
20
1.45
50
3.07
–38
0.19
–8
0.61
22
1.53
52
3.21
–36
0.21
–6
0.66
24
1.61
54
3.36
–34
0.23
–4
0.70
26
1.70
56
3.51
–32
0.25
–2
0.75
28
1.79
58
3.64
–30
0.27
0
0.80
30
1.89
60
3.83
–28
0.29
2
0.85
32
1.99
62
4.00
–26
0.32
4
0.91
34
2.09
64
4.17
–24
0.34
6
0.96
36
2.20
―
―
–22
0.37
8
1.02
38
2.31
―
―
4.00
3.
8
0
3.60
3.40
3.20
3.00
2.
8
0
2.60
2.40
2.20
2.00
1.
8
0
1.60
1.40
1.20
1.00
0.
8
0
0.60
0.40
0.20
0.00
3.90
3.70
3.50
3.30
3.10
2.90
2.70
2.50
2.30
2.10
1.90
1.70
1.50
1.30
1.10
0.90
0.70
0.50
0.30
0.10
–0.10
0
–10
–20
–30
–40
–50
10
20
30
40
50
60
Temperat
u
re ˚C
A
b
sol
u
te press
u
re (MP
a)
Press
u
re ga
u
ge
v
al
u
e (MP
a G)
Содержание VRV RXYMQ-A Series
Страница 1: ...Service Manual RXYMQ A Series Heat Pump 50 60 Hz SiME332106E...
Страница 283: ...SiME332106E Check Part 6 Service Diagnosis 277 PCB and Circuit Diagram U V W L3B L2B L1B P1 P2 N32...
Страница 296: ...SiME332106E 290 Part 7 Appendix 1 Wiring Diagrams 291 1 1 Outdoor Unit 291 1 2 VRV Indoor Unit 293 Part 7 Appendix...
Страница 297: ...SiME332106E Wiring Diagrams Part 7 Appendix 291 1 Wiring Diagrams 1 1 Outdoor Unit RXYMQ4AVMK C 3D133942...
Страница 298: ...Wiring Diagrams SiME332106E 292 Part 7 Appendix RXYMQ4 5 6AYFK C 3D133944A...
Страница 303: ...SiME332106E Wiring Diagrams Part 7 Appendix 297 FXMQ40 50 63 80 100ARV1 3D127112 04 59...