Field Settings for Outdoor Unit
SiME332106E
110
Part 5 Field Settings and Test Operation
(1) Microcomputer normal monitor
This monitor blinks while in normal control, and turns ON or OFF when an error occurs.
(2) 7 segment display
Used to check the transmission.
Used to display the transmission state between indoor and outdoor units.
Used to display the contents of error.
Used to display the contents of field setting.
(3) BS button
Used to change mode.
(4) DIP switch
Used to make field settings.
The figure below shows the required position of the DIP switches on spare PCB. Change DIP
switches at time of power disconnected.
RXYMQ4-6AYFK
(3) BS button (BS1~BS3)
(2) Segment display (SEG1~SEG3)
(4)
DIP switch
(DS1-1~4)
(DS2-1~4)
(1)
Microcomputer
normal monitor
(HAP)
Connection terminal
for transmission use
ON
OFF
1
2
3
4
DS1
Initial position of DIP switches (
)
1
2
3
4
DS2
Application model The setting method (
represents the position of switches)
RXYMQ4AVMK
Set DS1-2, DS1-4, DS2-1, and DS2-3 to ON.
RXYMQ4AYFK
RXYMQ5AYFK
RXYMQ6AYFK
Set DS1-2, DS1-4, DS2-1, DS2-2, and DS2-3 to
ON
ON
OFF
1 2 3 4
1 2 3 4
DS2
DS1
ON
OFF
1 2 3 4
1 2 3 4
DS1
DS2
Содержание VRV RXYMQ-A Series
Страница 1: ...Service Manual RXYMQ A Series Heat Pump 50 60 Hz SiME332106E...
Страница 283: ...SiME332106E Check Part 6 Service Diagnosis 277 PCB and Circuit Diagram U V W L3B L2B L1B P1 P2 N32...
Страница 296: ...SiME332106E 290 Part 7 Appendix 1 Wiring Diagrams 291 1 1 Outdoor Unit 291 1 2 VRV Indoor Unit 293 Part 7 Appendix...
Страница 297: ...SiME332106E Wiring Diagrams Part 7 Appendix 291 1 Wiring Diagrams 1 1 Outdoor Unit RXYMQ4AVMK C 3D133942...
Страница 298: ...Wiring Diagrams SiME332106E 292 Part 7 Appendix RXYMQ4 5 6AYFK C 3D133944A...
Страница 303: ...SiME332106E Wiring Diagrams Part 7 Appendix 297 FXMQ40 50 63 80 100ARV1 3D127112 04 59...