Troubleshooting by Error Code
SiME332106E
232
Part 6 Service Diagnosis
Note(s)
A
This is not the
LC
error.
Recheck the error code.
NO
YES
The service
monitor (green) on the
outdoor unit main
PCB (A1P) is
blinking.
NO
YES
The service
monitor (green) on the
inverter PCB (A3P) is
blinking.
Properly connect the connector.
NO
YES
Is the
connector between
the inverter PCB and the fan
PCB securely connected?
Replace the fan PCB (A4P).
NO
YES
The service
monitor (green) on the fan
PCB (A4P) is blinking.
NO
Replace the outdoor unit main PCB
(A1P).
YES
Continue operation.
The error could have resulted from
causes such as instantaneous
power failure.
The
LC
error recurs.
Replace all of the inverter PCB (A3P),
the fan PCB (A4P) and the noise filter
PCB (A2P).
YES
Replace the inverter PCB (A3P).
NO
The fuse of the
noise filter PCB has blown
out.
1. Connect and disconnect the connector once to ensure that it is securely connected.
Содержание VRV RXYMQ-A Series
Страница 1: ...Service Manual RXYMQ A Series Heat Pump 50 60 Hz SiME332106E...
Страница 283: ...SiME332106E Check Part 6 Service Diagnosis 277 PCB and Circuit Diagram U V W L3B L2B L1B P1 P2 N32...
Страница 296: ...SiME332106E 290 Part 7 Appendix 1 Wiring Diagrams 291 1 1 Outdoor Unit 291 1 2 VRV Indoor Unit 293 Part 7 Appendix...
Страница 297: ...SiME332106E Wiring Diagrams Part 7 Appendix 291 1 Wiring Diagrams 1 1 Outdoor Unit RXYMQ4AVMK C 3D133942...
Страница 298: ...Wiring Diagrams SiME332106E 292 Part 7 Appendix RXYMQ4 5 6AYFK C 3D133944A...
Страница 303: ...SiME332106E Wiring Diagrams Part 7 Appendix 297 FXMQ40 50 63 80 100ARV1 3D127112 04 59...