SiME332106E
Check
Part 6 Service Diagnosis
273
Note(s)
6.3 Superheat Operation Check
CHECK 3
Referring to the Fault Tree Analysis (FTA) shown below, probe the defective points
Abnormal piping length
Bent or crashed pipe
(Including moisture choke)
Stop valve closed.
Defective valve coil
Defective valve body
Defective valve coil
Defective valve body
Are the coil resistance and insulation normal?
Refer to
CHECK 7 .
Does the piping length fall in the permissible range?
Conduct visual checks.
Eliminate moisture by vacuum operation. (Refer to
CHECK 8 .
)
Check if the stop valve is open.
Defective
discharge
pipe
temperature
control
Defective hot
gas bypass
control
Hot gas circuit clogging
Defective solenoid
valve coil
Defective solenoid
valve body
Defective main PCB
Defective main
PCB
Defective valve coil
Defective low
pressure sensor
Defective subcooling
heat exchanger outlet
thermistor
Defective valve
body
Defective
subcooling
electronic
expansion
valve control
Superheat due to
shaft damage
Superheat due to
defective compressor
Defective indoor
unit electronic
expansion valve
Defective
control
Defective
control
Defective
outdoor unit
electronic
expansion valve
Defective four
way valve
operation
[In cooling only]
(
1)
Compressor
overheat
Refrigerant
shortage
High pipe
resistance
Defective
superheating
degree
control.
[In cooling]
If the indoor unit
electronic
expansion valve is
throttled too much:
(
2)
[In heating]
If the outdoor unit
electronic
expansion valve
excessively
throttled: (
3)
Temperature
increase of
discharge
pipe
Defective
subcooling
electronic
expansion
valve
Are the coil resistance and
insulation normal?
Is the connector properly connected?
Are the thermistor resistance characteristics
normal?
Are the voltage characteristics normal?
Is the pressure value checked with the
Service Checker corresponding to the
measurement value of the pressure sensor?
Check if the piping temperature connected
to the four way valve is normal.
Four way valve is in the
middle position.
Leak from hot gas bypass
valve
Defective
control
Defective gas pipe
thermistor of indoor unit
Defective thermistor for
indoor unit liquid pipe
Defective main
PCB
Defective low pressure
sensor
Defective suction pipe
thermistor
Defective main
PCB
Are the voltage characteristics normal?
Is the pressure value checked with the Service
Checker corresponding to the measurement
value of the pressure sensor?
Is the connector properly connected?
Are the thermistor resistance characteristics normal?
Is the connector properly connected?
Are the thermistor resistance characteristics normal?
Are the coil resistance and insulation normal?
Are the coil resistance and insulation normal?
Is the connector properly connected?
Are the thermistor resistance characteristics normal?
1. Refer to “Low pressure protection control” for hot gas bypass control.
2. “Superheating temperature control” in cooling is conducted by indoor unit electronic
expansion valve.
3. Superheating temperature control in heating is conducted by outdoor unit electronic
expansion valve (main).
Содержание VRV RXYMQ-A Series
Страница 1: ...Service Manual RXYMQ A Series Heat Pump 50 60 Hz SiME332106E...
Страница 283: ...SiME332106E Check Part 6 Service Diagnosis 277 PCB and Circuit Diagram U V W L3B L2B L1B P1 P2 N32...
Страница 296: ...SiME332106E 290 Part 7 Appendix 1 Wiring Diagrams 291 1 1 Outdoor Unit 291 1 2 VRV Indoor Unit 293 Part 7 Appendix...
Страница 297: ...SiME332106E Wiring Diagrams Part 7 Appendix 291 1 Wiring Diagrams 1 1 Outdoor Unit RXYMQ4AVMK C 3D133942...
Страница 298: ...Wiring Diagrams SiME332106E 292 Part 7 Appendix RXYMQ4 5 6AYFK C 3D133944A...
Страница 303: ...SiME332106E Wiring Diagrams Part 7 Appendix 297 FXMQ40 50 63 80 100ARV1 3D127112 04 59...