104 Commissioning
WAGO I/O SYSTEM 750 XTR
750-8202/040-001 PFC200 2ETH RS TELE XTR
Manual
Version 1.2.0, valid from FW Version 03.01.07(13)
7.3
Setting an IP Address
In the controller’s initial state, the following IP addresses are active for the
ETHERNET interface (Port X1 and Port X2):
Table 45: Default IP Addresses for ETHERNET Interfaces
ETHERNET Interface Default Setting
X1/X2
(switched mode)
Dynamic assignment of IP address using DHCP
(“Dynamic Host Configuration Protocol”)
Adapt IP addressing to your specific system structure to ensure that the PC and
the controller can communicate with one another using one of the available
configuration tools (WBM, WAGO ETHERNET Settings or CBM – see section
“Configuration”).
Example for incorporating the controller (192.168.2.17) into an existing
network:
•
The IP address of the host PC is
192.168.1.2
.
•
The controller and host PC must be in the same subnet (regardless of the
IP address of the host PC).
•
With a subnet mast of
255.255.255.0
, the first three digits of the IP address
of the host PC and controller must match so that they are located in the
same subnet.
Table 46: Network Mask 255.255.255.0
Host PC
Subnet Address Range for the Controller
192.168.1
.2
192.168.1
.1 or
192.168.1
.3 …
192.168.1
.254