WAGO I/O SYSTEM 750 XTR
Commissioning 125
750-8202/040-001 PFC200 2ETH RS TELE XTR
Manual
Version 1.2.0, valid from FW Version 03.01.07(13)
7.8.1.5 “PLC WebVisu” Page
The settings for the web visualization created in the runtime system are shown
on the “PLC WebVisu” page.
7.8.1.5.1 “Web Server Configuration” Group
Table 54: WBM “PLC WebVisu” Page – “Web Server Configuration” Group
Parameters
Explanation
CODESYS 2 Webserver
State
This indicates the status (enabled/disabled) of the
CODESYS 2 web server.
e!
RUNTIME
Webserver
State
This indicates the status (enabled/disabled) of the
e!
RUNTIME
web server.
Default Webserver
Choose here whether the Web-based Management
or web visualization of the runtime system should be
displayed when only entering the IP address of the
controller.
Web-based
Management
The Web-based Management is
displayed.
Web-Visu
The web visualization of the runtime
system is displayed.
Click
[Submit]
to apply change. The change is effective immediately.
In its default setting, the WBM is called up when only entering the IP address.
To update the display after switching, enter the IP address again in the address
line of the web browser.
To display the web visualization, the web server must be enabled (in WBM under
“Ports and Services” -> “PLC Runtime Services”) and there must be a suitably
configured application.
Regardless of the default web server setting, the WBM can be called up at any
time with “https://<IP address>/wbm” and the web visualization with
“https://<IP address>/webvisu.”
You can obtain additional information on CODESYS 2 web visualization in the
section of the same name.
Possible error messages when calling up the web visualization
The “500 − Internal Server Error” message indicates that the web server is not
enabled.
A page with the header “WebVisu not available” means that no application has
been loaded in the controller using web visualization.