WAGO I/O SYSTEM 750 XTR
Device Description 51
750-8202/040-001 PFC200 2ETH RS TELE XTR
Manual
Version 1.2.0, valid from FW Version 03.01.07(13)
3.8.10 Mechanical Conditions
Table 27: Technical Data – Mechanical Conditions
Vibration resistance
Max. 5g
*
*
Follow the installation instructions
3.8.11 Climatic Environmental Conditions
Table 28
: Technical Data ‒ Climatic Environmental Conditions
Surrounding air temperature, operation
−40 °C … +70 °C
Surrounding air temperature, storage
−40 °C … +85 °C
Relative humidity
*)
95 %
Elevation above sea level
without temperature derating
with temperature derating
max.
0 m … 2000 m
2000 m … 5000 m: 0.5 K per 100 m
5000 m
Resistance to harmful substances
Acc. to IEC 60068-2-42 and
IEC 60068-2-43
Maximum pollutant concentration at
relative humidity < 75
%
SO
2
≤
25 ppm
H
2
S
≤
10 ppm
Special conditions
• Ensure that the permissible
temperature range of the
connecting cable is correct
dimensioned depending on the
installation position and current
intensity, because the clamping
point temperature at 10 A can be
up to 25
°C above the expected
surrounding air temperature.
*)
Short-term condensation acc. class 3K7 / IEC EN 60721-3-3 permitted, applying
E-DIN 40046-721-3 (except wind-driven precipitation, water and ice formation)
Limited temperature range in vertical position!
When mounted vertically, a maximum surrounding air
temperature of 65 °C must
not be exceeded! Otherwise, the functionality of the device cannot be ensured
and the device may be damaged.