WAGO I/O SYSTEM 750 XTR
Commissioning 115
750-8202/040-001 PFC200 2ETH RS TELE XTR
Manual
Version 1.2.0, valid from FW Version 03.01.07(13)
</dg_
7.7
Initiating Reset Functions
You can initiate various reset functions using the mode selector switch and the
Reset button (RST).
7.7.1
Warm Start Reset
</dg_
The CODESYS 2 application is reset on a warm start reset. This corresponds to
the WAGO I/O PRO IDE “Reset” command.
</dg_
To perform a warm start reset, set the mode selector switch to "Reset" and hold it
there for two to seven seconds.
Execution of the reset is signaled by the red “RUN LED” briefly going out when
the mode selector switch is released.
7.7.2
Cold Start Reset
</dg_
On a cold start reset the CODESYS 2 application is reset and the memory
containing the retain variables is cleared.
This corresponds to the WAGO I/O PRO IDE “Reset (Cold)” command.
</dg_
To perform a cold start reset, set the mode selector switch to “Reset” and hold it
there for more than seven seconds.
Execution of the reset is signaled after seven seconds by the “RUN” LED going
out for an extended period. You can then release the mode selector switch.
</dg_
7.7.3
Software Reset
The controller is restarted on a software reset.
To perform a software reset, set the mode selector switch to RUN or STOP and
then press the Reset button (RST) for one to eight seconds.
Reset completion is indicated by a brief orange flashing of all LEDs. After a few
seconds the SYS LED will indicate successful boot-up of the controller.