WAGO I/O SYSTEM 750 XTR
Appendix 383
750-8202/040-001 PFC200 2ETH RS TELE XTR
Manual
Version 1.2.0, valid from FW Version 03.01.07(13)
Table 287: Description of Configuration Scripts for “SNMP”
Parameters Status Call-Up
Output/Input
Valid
SNMP Trap Receiver Configuration for v1 and v2c
Any number of trap receivers can be configured. A trap receiver that has been set up is always
active; the data set must be completely deleted to deactivate it.
IP address of a
trap receiver
read
get_snmp_data
v1-v2c-trap-receiver-
address <Nummer>
Specifies the IP address of the
trap receiver that the controller is
to send the v1 or v2 traps to.
The <number> parameter
enables consecutive reading of
related data from the individually
configured trap receiver for a
short period of time (without
interim changing of the data).
This is a consecutive number that
is not connected to the data. If
the number is not included, the
data of the first receiver are read.
Right
away
Community
Name
read
get_snmp_data
v1-v2c-trap-receiver-
community-name
<Nummer>
Specifies the community name
that the SNMP agent of the
controller sends in the Trap
Header.
Parameter <number> see section
“IP Address of a Trap Receiver”.
Right
away
Trap version
read
get_snmp_data
v1-v2c-trap-receiver-
version <Nummer>
Specifies the SNMP version (“v1”
or “v2c”) via which the SNMP
agent sends the traps to the
associated trap receiver address.
Parameter <number> see section
“IP Address of a Trap Receiver”.
Right
away
Creating/
deleting a trap
receiver
write
config_snmp
v1-v2c-trap-receiver-
edit=<Value1>
v1-v2c-trap-receiver-
address=<Value2>
v1-v2c-trap-receiver-
community-
name=<Value3>
v1-v2c-trap-receiver-
version=<Value4>
Create a new trap receiver
(value1=add) or delete an
already configured trap receiver
(value1=delete).
Other parameters:
<Value2> = IP address
(number.number.number.number
) that the controller is to send the
traps to.
<Value3>: Community string
(string), which the controller
enters in the trap header.
<Value4>: SNMP version, via
which the traps are sent (v1 or
v2c).
Note:
All parameters must also be
entered when deleting a trap
receiver, as this is the only
means to uniquely identify the
data set.
After
restart