WAGO I/O SYSTEM 750 XTR
Service 337
750-8202/040-001 PFC200 2ETH RS TELE XTR
Manual
Version 1.2.0, valid from FW Version 03.01.07(13)
11.2.3 Factory Reset
Do not switch the controller off!
The controller can be damaged by interrupting the factory reset process.
Do not switch the controller off during the factory reset process, and do not
disconnect the power supply!
All parameters and passwords are overwritten!
All controller parameters and passwords are overwritten by a factory reset.
Stored boot projects are deleted, including existing web visualization data.
Subsequently installed firmware functions are not overwritten.
If you have any questions, contact WAGO Support.
The controller is restarted after the factory reset.
Proceed as follows to factory reset the controller:
1.
Press the Reset button (RST).
2.
Set the mode selector switch to the “RESET” position.
3.
Press and hold both buttons until the “SYS” LED alternately flashes
red/green after approx. 8 seconds.
4.
When the “SYS” LED flashes red/green alternately, release the mode
selector switch and Reset button.
Do not interrupt the reset process!
If you release the Reset button (RST) too early, then the controller restarts
without performing the factory reset.