376 Appendix
WAGO I/O SYSTEM 750 XTR
750-8202/040-001 PFC200 2ETH RS TELE XTR
Manual
Version 1.2.0, valid from FW Version 03.01.07(13)
Table 282: Description of the Configuration Scripts for "Administration"
Parameters Status Call
Output/Input
Effecti
ve
Configuration of Service Interface
Configuration of
Service
Interface
read
get_service_interface_
config mode
User of the serial interface.
Active: Current value
Configured: Value set, but not
applied by a reboot
Possible return values are:
- service (WAGO-I/O-
CHECK
,
WAGO-I/O-
PRO
,
e!
COCKPIT
)
- linux (Linux
®
console)
- free (unused, free for
application)
immedia
tely
write
config_service_interface
_config mode=<value>
User of the serial interface.
Possible entries for <value>:
- service
- linux
- free
after
Restart
Reboot Controller
-
write
start_reboot
Restart the controller.
immedia
tely
</dg_
Table 283: Description of Configuration Scripts for “Package Server”
Parameters Status Call-Up
Output/Input
Valid
Firmware Update
Medium for
active partition read
get_filesystem_data
active-partition-medium
Specifies the medium for the
active partition
(sd-card, internal-flash-nand).
Right
away
Create
firmware
backup
write
firmware_backup
package-
settings=<Value1>
package-
codesys=<Value2>
package-
system=<Value3>
device-
medium=<Value4>
auto-update=<Value5>
download-dir=<Value6>
Generates a backup of the
selected packet on the specified
medium.
Parameter:
<Value1> = 1, if the “Settings”
package is to be selected.
<Value2> = 1, if the “CODESYS
Project” package is to be
selected.
<Value3> = 1, if the “System”
package is to be selected.
<Value4> = target medium for
saving the backup. (sd-card,
network)
<Value5> = 1, if “Auto Update”
function is to be activated.
<Value6> = target directory for
backup file, if “network” is
selected as target medium.
Parameters, which are not to be
set (1) can either be set to 0 or
omitted completely.
Right
away
</dg_