242 Run-time System CODESYS 2.3
WAGO I/O SYSTEM 750 XTR
750-8202/040-001 PFC200 2ETH RS TELE XTR
Manual
Version 1.2.0, valid from FW Version 03.01.07(13)
3.
Right-click on the entry “K-
Bus[FIX]
” and then select “Edit” in the contextual
menu. The “configuration” dialog window then opens.
Figure 57: Control Configuration – Edit
4.
There are three options for accepting the topology for the I/O modules
connected to the fieldbus controller. The simplest way is to scan in the
topology using WAGO-I/O-
CHECK
.
To do this, click on the “Start WAGO-I/O-
CHECK
and scan” button.
Figure 58: “Start WAGO-I/O-
CHECK
and Scan” Button
Ensure proper installation of WAGO-I/O-
CHECK
!
This function requires that the latest version of WAGO-I/O-
CHECK
be installed
and the IP address set under “Online > Communication parameters”, as
otherwise communication will not be possible.