WAGO I/O SYSTEM 750 XTR
Diagnostics 319
750-8202/040-001 PFC200 2ETH RS TELE XTR
Manual
Version 1.2.0, valid from FW Version 03.01.07(13)
The RUN LED indication depends on the runtime system enabled (CODESYS 2
or
e!
RUNTIME
).
The following indications apply to the CODESYS 2 runtime system:
Table 230: Diagnostics RUN LED
Status
Explanation
Solution
Green
PLC program has the
status “Run”.
---
Green flashing PLC program at a
debug point.
Resume the program in the linked IDE
(Integrated Development Environment)
using “Single step” or “Start”. If the
connection has been interrupted, set the
Run/Stop switch to “Stop” and then back
to “Run” to enable the program to
continue.
Green/red
flashing
PLC is at a debug
point and the
Run/Stop switch has
been set to “Stop”.
Set the Run/Stop switch to “Run” to
enable the program to continue.
Red
No PLC-program
loaded or PLC
program has the
status “Stop”.
Load the PLC program.
Set the Run/Stop switch to “Run” to start
the current program.