WAGO I/O SYSTEM 750 XTR
Modbus – CODESYS 2 289
750-8202/040-001 PFC200 2ETH RS TELE XTR
Manual
Version 1.2.0, valid from FW Version 03.01.07(13)
9.3.2
Modbus TCP Settings
The “Modbus TCP Settings” contains the following configuration parameters for
the “Modbus TCP” mode:
Table 213: Modbus TCP Settings
Parameters Explanation
TCP mode
Enable for the Modbus TCP mode
Off
Operation not permitted
Active
*
Operation possible
TCP port
Port number for the TCP link
1
Minimum port number
502
*
Modbus default port
65535
Maximum port number
TCP Timeout Time-out for a TCP link
1
100 ms (1 × 100 ms)
600
*
60 seconds (600 × 100ms)
65535
1 h 49 min 13 s 500 ms (65535 × 100 ms)
*
Default setting
9.3.3
Modbus UDP Settings
The “Modbus UDP Settings” group contains the following configuration
parameters for the “Modbus UDP” mode:
Table 214: Modbus UDP Settings
Parameters Explanation
UDP mode
Enable for the Modbus UDP mode
Off
Operation not permitted
Active
*
Operation possible
UDP port
Port number for the UDP link
1
Minimum port number
502
*
Modbus default port
65535
Maximum port number
*