7.3.4
Temporarily Setting a Fixed IP Address
This procedure temporarily sets the IP address for the X1 interface to the fixed
address “192.168.1.17”.
When the switch is enabled, the fixed address is also used for interface X2.
When the switch is disabled, the original address setting for interface X2 is not
changed.
No reset is performed.
To make this setting, proceed as follows:
1.
Set the mode selector switch to STOP and
2.
Press and hold the Reset button (RST) for longer than 8 seconds.
Execution of the setting is signaled by the “SYS” LED flashing orange.
To cancel this setting, proceed as follows:
•
Perform a software reset or
•
Switch off the controller and then switch it back on.