WAGO I/O SYSTEM 750 XTR
Modbus – CODESYS 2 313
750-8202/040-001 PFC200 2ETH RS TELE XTR
Manual
Version 1.2.0, valid from FW Version 03.01.07(13)
Table 225: Diagnostics for the Error Server
Diagnostics
ID
Diagnostic text
Method of
saving
Explanation
0x00090006 Modbus Slave
UDP start failed
Permanent Starting the Modbus slave in
UDP mode failed.
0x00090007 Modbus Slave
UDP terminated
Temporary Modbus slave UDP mode
successfully terminated.
0x00090008 Modbus Slave
RTU started
Temporary Modbus slave successfully
started in the RTU mode.
0x00090009 Modbus Slave
RTU start failed
Permanent Starting the Modbus slave in
RTU mode failed.
0x0009000A Modbus Slave
RTU terminated
Temporary Modbus slave RTU mode
successfully terminated.
0x0009000B Modbus Slave
data exchange
started by PLC
Temporary Modbus slave data exchange
started.
0x0009000C Modbus Slave
data exchange
stopped by PLC
Temporary Modbus slave data exchange
stopped.
0x0009000F Modbus Slave
PLC watchdog
timer expired
Permanent Monitoring time for controller
(PLC) expired.
0x00090100 Modbus Slave
common
configuration
failed.
Permanent Modbus slave configuration
failed.
0x00090101 Modbus Slave
TCP configured
successfully.
Temporary Modbus slave TCP
configuration completed
successfully.
0x00090102 Modbus Slave
TCP configuration
failed.
Permanent Modbus slave TCP
configuration failed.
0x00090103 Modbus Slave
UDP configured
successfully
Temporary Modbus slave UDP
configuration completed
successfully.
0x00090104 Modbus Slave
UDP configuration
failed.
Permanent Modbus slave UDP
configuration failed.
0x00090105 Modbus Slave
RTU configured
successfully.
Temporary Modbus slave RTU
configuration completed
successfully.
0x00090106 Modbus Slave
RTU configuration
failed
Permanent Modbus slave RTU
configuration failed.
0x00090107 Port for Modbus
Slave RTU
operation not free.
Permanent Serial port for Modbus slave
RTU configuration already
occupied.