314 Modbus – CODESYS 2
WAGO I/O SYSTEM 750 XTR
750-8202/040-001 PFC200 2ETH RS TELE XTR
Manual
Version 1.2.0, valid from FW Version 03.01.07(13)
Table 225: Diagnostics for the Error Server
Diagnostics
ID
Diagnostic text
Method of
saving
Explanation
0x00090108 Modbus Slave
RTU configuration
in RS-485 mode
failed.
Permanent Modbus slave RTU
configuration for the RS-485
mode has failed.
0x00090200 Modbus Slave
Watchdog
activated.
Temporary Modbus watchdog activated.
0x00090201 Modbus Slave
Watchdog
deactivated.
Temporary Modbus watchdog
deactivated.
0x00090202 Modbus Slave
Watchdog Timer
expired.
Permanent Modbus watchdog monitoring
time expired.
0x00090203 Modbus Slave has
terminated all
established TCP
connections.
Permanent All Modbus TCP connections
terminated due to timeout.
0x00090300 Modbus Slave:
obtaining system
resource failed
Permanent Request for system resources
by the Modbus slave has
failed.
0x00090301 Modbus Slave:
processing system
resource failed.
Permanent Access to system resources
by the Modbus slave has
failed.