Error
Code
Diag.
Code
Device
Display
Meaning for the LMV5x System
Corrective Action
Any #
Stack error
01
Stack overflow
02
Value dropped below preset minimum limit
03
Test values in stack range exceeded
53
01
Faulty reset state has occurred
Any #
Invalid parameter setting.
See corrective action based on diagnostic code.
00
AND NOT ("& /") settings are not permitted in the gas
extraneous light phases
Correct the setting for the
SensExtralGas
parameter.
01
AND NOT ("& /") settings are not permitted in the oil
extraneous light phases
Correct the setting for the
SensExtralOil
parameter.
02
AND NOT ("& /") settings are not permitted in the gas pilot
phases
Correct the setting for the
SensPilotPhGas
parameter.
03
AND NOT ("& /") settings are not permitted in the oil pilot
phases
Correct the setting for the
SensPilotPhOil
parameter.
04
AND NOT ("& /") settings are not permitted in the gas operating
phases
Correct the setting for the
SensOperPhGas
parameter.
05
AND NOT ("& /") settings are not permitted in the oil operating
phases
Correct the setting for the
SensOperPhOil
parameter.
06
The temperature-compensated flue gas recirculation function is
not permitted
This function is only enabled for the LMV52.4. Setting
FGR-Mode
to Temp.comp, TCautoDeact, deactMinpos,
or auto deact. is not permitted.
07
The high-temperature flame safeguard function is not permitted
This function is only enabled for the LMV50. Setting
HeavyOilDirStart
to "HTempGuard" is not permitted.
08
The external flame safeguard function is not permitted
This function is only enabled for the LMV50 and
LMV52. Setting
HeavyOilDirStart
to "ext.FlameGd" is
not permitted.
09
The flue gas recirculation function is not permitted
This function is only enabled for the LMV50, LMV51.3,
and LMV52. Changing
FGR-Mode
from "deactivated"
is not permitted.
0A
The VSD / auxiliary actuator 3 function is not permitted
This function is only enabled for the LMV50, LMV51.3,
and LMV52. Setting
AuxActuator
to VSD and / or
AUX3 is not permitted.
0B
The cooling in standby function is not permitted
This function is only enabled for the LMV50. Setting
Config X5-03
to "CoolfctStby" is not permitted.
0C
X5-03 double assignment: External load controller via contact
(operating mode 1) / deactivation O2 and startup stop phase 36
Adjust
LC_OptgMode
or
Config X5-03
to prevent the
double assignment.
Fault with Base Unit (LMV5)
52
If fault occurs sporadically, reduce electrical noise.
If fault occurs continuously, replace LMV5.
LMV5
Internal Fault
Basic Unit
Invalid
parameterization
57
Section 7
Page 37
SCC Inc.
HOME
HOME
Summary of Contents for LMV 5 Series
Page 2: ...Intentionally Left Blank ...
Page 41: ...LMV Series Technical Instructions Document No LV5 1000 SCC Inc Page 7 Section 2 HOME ...
Page 42: ...Technical Instructions LMV Series Document No LV5 1000 Section 2 Page 8 SCC Inc HOME ...
Page 43: ...LMV Series Technical Instructions Document No LV5 1000 SCC Inc Page 9 Section 2 HOME ...
Page 44: ...Technical Instructions LMV Series Document No LV5 1000 Section 2 Page 10 SCC Inc HOME ...
Page 45: ...LMV Series Technical Instructions Document No LV5 1000 SCC Inc Page 11 Section 2 HOME ...
Page 46: ...Technical Instructions LMV Series Document No LV5 1000 Section 2 Page 12 SCC Inc HOME ...
Page 47: ...LMV Series Technical Instructions Document No LV5 1000 SCC Inc Page 13 Section 2 HOME ...
Page 48: ...Technical Instructions LMV Series Document No LV5 1000 Section 2 Page 14 SCC Inc HOME ...
Page 49: ...LMV Series Technical Instructions Document No LV5 1000 SCC Inc Page 15 Section 2 HOME ...
Page 50: ...Technical Instructions LMV Series Document No LV5 1000 Section 2 Page 16 SCC Inc HOME ...
Page 51: ...LMV Series Technical Instructions Document No LV5 1000 SCC Inc Page 17 Section 2 HOME ...
Page 52: ...Technical Instructions LMV Series Document No LV5 1000 Section 2 Page 18 SCC Inc HOME ...
Page 53: ...LMV Series Technical Instructions Document No LV5 1000 SCC Inc Page 19 Section 2 HOME ...
Page 54: ...Technical Instructions LMV Series Document No LV5 1000 Section 2 Page 20 SCC Inc HOME ...
Page 55: ...LMV Series Technical Instructions Document No LV5 1000 SCC Inc Page 21 Section 2 HOME ...
Page 373: ...Intentionally Left Blank ...