LMV Series
Technical Instructions
LV5-1000
Menu Path
Parameter
Default
Range
Description
51.1
52.2
52.4
LEGEND -
Password Access:
(U)=User, (S)=Service, (O)=OEM, Shaded = Commonly Used, ** = Must Set, X = Has Function, / = Partial Function
LMV
O2Ctrl/LimitrGas (S)
O2Ctrl/LimitrOil (S)
LC Analog Output (S)
Load
See
Description
See:
Params & Display > LoadController > Configuration > Analog Output > OutValuSelection
x x x
allowed Pot.diff (S)
15
10-15
Sets the allowable difference between channels A and B of the actuator's potentiometer.
Units are tenths of a degree, so 10 = 1.0 degrees.
x x x
OptgMode COx Gas (S)
deact
x
OptgMode COx Oil (S)
deact
x
AirTempX60PT1000 (O)
deact
activated
deactivated
See:
Params & Display > O2 Module> Configuration > AirTempX60PT1000
x x
GasFiring (U)
Hours run firing gas. Can be adjusted here. See:
Operation > HoursRun
x x x
OilStage1/Mod (U)
Hours run on modulating or stage 1 oil. Can be adjusted here. See:
Operation > HoursRun
x x x
OilStage2 (U)
Hours run on stage 2 oil. Can be adjusted here. See:
Operation > HoursRun
x x x
OilStage3 (U)
Hours run on stage 3 oil. Can be adjusted here. See:
Operation > HoursRun
x x x
TotalHoursReset (U)
Hours run on all fuels. Can be adjusted here. See:
Operation > HoursRun
x x x
TotalHours (U)
x x x
SystemOnPower (U)
x x x
GasFiring (U)
Hours run firing gas. Can be reset here. See:
Operation > HoursRun
x x x
OilStage1/Mod (U)
Hours run on modulating or stage 1 oil. Can be reset here. See:
Operation > HoursRun
x x x
OilStage2 (U)
Hours run on stage 2 oil. Can be reset here. See:
Operation > HoursRun
x x x
OilStage3 (U)
Hours run on stage 3 oil. Can be reset here. See:
Operation > HoursRun
x x x
TotalHoursReset (U)
Hours run on all fuels. Can be reset here. See:
Operation > HoursRun
x x x
GasStartCount (U)
Number of starts for gas. Can be adjusted here. See:
Operation > StartCounter
x x x
OilStartCount (U)
Number of starts for oil. Can be adjusted here. See:
Operation > StartCounter
x x x
TotalStartCountR (U)
Total number of starts. Can be adjusted here. See:
Operation > StartCounter
x x x
TotalStartCount (U)
Total number of starts. Cannot be reset.
x x x
GasStartCount (U)
Number of starts for gas. Can be reset here. See:
Operation > StartCounter
x x x
OilStartCount (U)
Number of starts for oil. Can be reset here. See:
Operation > StartCounter
x x x
TotalStartCountR (U)
Total number of starts. Can be reset here. See:
Operation > StartCounter
x x x
x x
Params & Display>
HoursRun>
These values CANNOT be adjusted or reset. See:
Operation > HoursRun
Params & Display>
HoursRun>
Reset
Params & Display>
StartCounter
Read Only
0
0-999999 hr
deactivated
COx Control
COx Limiter
Future functionality. Does nothing at this time.
Reset Only
Reset Only
Params & Display>
SystemConfig
Read Only
See:
Params & Display > O2Contr/Alarm > GasSettings > OptgMode
man deact
See
Description
Read Only
Params & Display>
StartCounter>
Reset
0
0-999999 hr
SCC Inc.
Page 44
Section 3
HOME
HOME
P - LIST
Summary of Contents for LMV 5 Series
Page 2: ...Intentionally Left Blank ...
Page 41: ...LMV Series Technical Instructions Document No LV5 1000 SCC Inc Page 7 Section 2 HOME ...
Page 42: ...Technical Instructions LMV Series Document No LV5 1000 Section 2 Page 8 SCC Inc HOME ...
Page 43: ...LMV Series Technical Instructions Document No LV5 1000 SCC Inc Page 9 Section 2 HOME ...
Page 44: ...Technical Instructions LMV Series Document No LV5 1000 Section 2 Page 10 SCC Inc HOME ...
Page 45: ...LMV Series Technical Instructions Document No LV5 1000 SCC Inc Page 11 Section 2 HOME ...
Page 46: ...Technical Instructions LMV Series Document No LV5 1000 Section 2 Page 12 SCC Inc HOME ...
Page 47: ...LMV Series Technical Instructions Document No LV5 1000 SCC Inc Page 13 Section 2 HOME ...
Page 48: ...Technical Instructions LMV Series Document No LV5 1000 Section 2 Page 14 SCC Inc HOME ...
Page 49: ...LMV Series Technical Instructions Document No LV5 1000 SCC Inc Page 15 Section 2 HOME ...
Page 50: ...Technical Instructions LMV Series Document No LV5 1000 Section 2 Page 16 SCC Inc HOME ...
Page 51: ...LMV Series Technical Instructions Document No LV5 1000 SCC Inc Page 17 Section 2 HOME ...
Page 52: ...Technical Instructions LMV Series Document No LV5 1000 Section 2 Page 18 SCC Inc HOME ...
Page 53: ...LMV Series Technical Instructions Document No LV5 1000 SCC Inc Page 19 Section 2 HOME ...
Page 54: ...Technical Instructions LMV Series Document No LV5 1000 Section 2 Page 20 SCC Inc HOME ...
Page 55: ...LMV Series Technical Instructions Document No LV5 1000 SCC Inc Page 21 Section 2 HOME ...
Page 373: ...Intentionally Left Blank ...