![background image](http://html1.mh-extra.com/html/omron/r88d-gt-series/r88d-gt-series_user-manual_742798270.webp)
4-35
4-3 Wiring Conforming to EMC Directives
4
System Design
Noise Filters for the Power Supply Input
• Use the following noise filters for the Servo Drive's power supply.
Dimensions
SUP-EK5-ER-6
3SUP-HQ10-ER-6
Servo Drive model
Noise filter for the power supply Input
Model
Rated
current
Max. leakage
current (60 Hz)
Manufacturer
R88D-GTA5L
SUP-EK5-ER-6
5 A
1 mA
(at 250 VAC)
Okaya Electric
Industries Co.,
Ltd.
R88D-GT01L
R88D-GT02L
R88D-GT04L
3SUP-HQ10-ER-6
10 A
3.5 mA
(at 500 VAC)
R88D-GT01H
SUP-EK5-ER-6
5 A
1 mA
(at 250 VAC)
R88D-GT02H
R88D-GT04H
R88D-GT08H
3SUP-HQ10-ER-6
10 A
3.5 mA
(at 500 VAC)
R88D-GT10H
3SUP-HU30-ER-6
30 A
3.5 mA
(at 500 VAC)
R88D-GT15H
R88D-GT20H
R88D-GT30H
3SUP-HL50-ER-6B
50 A
8 mA
(at 500 VAC)
R88D-GT50H
R88D-GT75H
105
115
5.5
43
70
52
10
95
M4
M3
M4
Ground
terminal
Cover mounting
screw
Cover
Noise Filter
50.0
60.0
12.0
10.0
11.6
13.0
75.0
7.0
2.0
88.0
100
±
2.0
53.1
±
2.0
5.0
Two, 4.5
×
6.75 dia.
Two, 4.5 dia. Six, M4
Summary of Contents for R88D-GT series
Page 20: ...18 Table of Contents ...
Page 234: ...3 133 3 8 Reactor Specifications 3 Specifications ...
Page 448: ...7 37 7 5 Manual Tuning 7 Adjustment Functions ...
Page 474: ...8 25 8 5 Periodic Maintenance 8 Troubleshooting ...
Page 475: ...Chapter 9 Appendix 9 1 Connection Examples 9 1 9 2 Parameter Tables 9 11 ...
Page 509: ......