XtraDrive User Manual
Chapter 3: Wiring
3-28
3.6. Examples of Standard Connections
The following diagrams show examples of standard servo amplifier
connections by specifications and type of control.
Note for single-phase power supply specifications:
XtraDrive XD-08** have changed from three-phase specifications to single-
phase. Main circuit connection terminals (L1, L2, L3) remained.
These devices have terminal B3 and internal regenerative resistor. Observe
the following points.
1. Connect main power supply shown below to L1 and L3 terminals. Power
supply is single-phase, 220 to 230 VAC +10% to –15%, 50/60Hz. If
power supply of 187V (-15% of220V) or less is used, alarm A41
indicating voltage shortage, may occur when accelerating to max speed
with max torque of motor.
2. Short-circuit B2 and B3 terminals using the internal regenerative resistor.
If capacity of the regenerative resistor is insufficient, remove the lead
between B2 and B3 terminals and connect an external regenerative
resistor unit to B1 and B2 terminals.
Summary of Contents for 8U0108-E1-01
Page 4: ...iv This page intentionally left blank...
Page 6: ...vi This page intentionally left blank...
Page 12: ...XtraDrive User Manual Table of Contents Preface xii This page intentionally left blank...
Page 27: ...XtraDrive User Manual Chapter 3 Wiring 3 3 3 1 1 Single Phase 200V Main Circuit Specifications...
Page 29: ...XtraDrive User Manual Chapter 3 Wiring 3 5 3 1 3 Three phase 200V Main Circuit Specifications...
Page 30: ...XtraDrive User Manual Chapter 3 Wiring 3 6 3 1 4 Three Phase 400V Main Circuit Specifications...
Page 32: ...XtraDrive User Manual Chapter 3 Wiring 3 8 3 2 2 Three phase 1kW to 3kW 200V Models...
Page 33: ...XtraDrive User Manual Chapter 3 Wiring 3 9 3 2 3 Three phase 0 5kW to 3 0kW 400V Models...
Page 56: ...XtraDrive User Manual Chapter 3 Wiring 3 32 This page intentionally left blank...
Page 332: ......