XtraDrive User Manual
Chapter
5
: Parameter Settings and Functions
5-87
Incremental Pulses and Origin Pulses
Just as with normal incremental pulses, initial incremental pulses which
provide absolute data are first divided by the frequency divider inside
the servo amplifier and then output.
Setting the Pulse Dividing Ratio
Use the following parameter to set the pulse-dividing ratio.
Parameter
Signal
Setting (PPR)
Description
Setting Range: 16 to 16384 Speed/Torque Control,
Pn201 PG
Divider
Default Setting: 16384
Position Control
This parameter sets the number of output pulses for PG output signals
(PAO, /PAO, PBO, /PBO).
Pulses from the motor encoder (PG) are divided by the number of
pulses set here before being output.
The set value is the number of output pulses per revolution. Set this
value according to the reference unit of the machine or controller to be
used.
The setting range varies according to the encoder used.
Summary of Contents for 8U0108-E1-01
Page 4: ...iv This page intentionally left blank...
Page 6: ...vi This page intentionally left blank...
Page 12: ...XtraDrive User Manual Table of Contents Preface xii This page intentionally left blank...
Page 27: ...XtraDrive User Manual Chapter 3 Wiring 3 3 3 1 1 Single Phase 200V Main Circuit Specifications...
Page 29: ...XtraDrive User Manual Chapter 3 Wiring 3 5 3 1 3 Three phase 200V Main Circuit Specifications...
Page 30: ...XtraDrive User Manual Chapter 3 Wiring 3 6 3 1 4 Three Phase 400V Main Circuit Specifications...
Page 32: ...XtraDrive User Manual Chapter 3 Wiring 3 8 3 2 2 Three phase 1kW to 3kW 200V Models...
Page 33: ...XtraDrive User Manual Chapter 3 Wiring 3 9 3 2 3 Three phase 0 5kW to 3 0kW 400V Models...
Page 56: ...XtraDrive User Manual Chapter 3 Wiring 3 32 This page intentionally left blank...
Page 332: ......