XtraDrive User Manual
Chapter 7: Using the Panel Operator
7-37
3.
Press the DATA/SHIFT key for a minimum of one second, and the
display will be as shown below.
4.
Input the value (0001) and press the
MODE/SET
key. The display
will change as shown below and the write protection will be
established.
Flashing for
one second
5.
Press the DATA/SHIFT key for a minimum of one second to return
to the Auxiliary Function mode display.
This completes the procedure for setting the write protection. The new
password setting will be valid after the next power OFF/ON cycle.
7.2.13. Clearing the Option Unit Detection Alarm
Alarm A.E7 (option unit detection failure) occurs the first time that the
XtraDrive servo amplifier is turned ON after disconnecting an option
board.
IMPORTANT
•
Initialize the parameter settings with the servo OFF.
•
After performing the procedure, cycle the power to reset all parameters to the default settings.
•
Because the parameter has been set for the XtraDrive connected to an option board,
be sure to adjust the setting or initialize the parameter value (Fn005 of the Auxiliary Function
mode) to meet the current system needs.
Summary of Contents for 8U0108-E1-01
Page 4: ...iv This page intentionally left blank...
Page 6: ...vi This page intentionally left blank...
Page 12: ...XtraDrive User Manual Table of Contents Preface xii This page intentionally left blank...
Page 27: ...XtraDrive User Manual Chapter 3 Wiring 3 3 3 1 1 Single Phase 200V Main Circuit Specifications...
Page 29: ...XtraDrive User Manual Chapter 3 Wiring 3 5 3 1 3 Three phase 200V Main Circuit Specifications...
Page 30: ...XtraDrive User Manual Chapter 3 Wiring 3 6 3 1 4 Three Phase 400V Main Circuit Specifications...
Page 32: ...XtraDrive User Manual Chapter 3 Wiring 3 8 3 2 2 Three phase 1kW to 3kW 200V Models...
Page 33: ...XtraDrive User Manual Chapter 3 Wiring 3 9 3 2 3 Three phase 0 5kW to 3 0kW 400V Models...
Page 56: ...XtraDrive User Manual Chapter 3 Wiring 3 32 This page intentionally left blank...
Page 332: ......