XtraDrive User Manual
Chapter 2: Installation
2-2
2.1. Servo
Amplifiers
The XtraDrive servo amplifiers are base-mounted. Incorrect installation will
cause problems. Follow the installation instructions below.
2.1.1. Storage
Conditions
Store the servo amplifier within the following temperature range, as
long as it is stored with the power cable disconnected.
-20 to 85°C
2.1.2. Installation
Site
The following precautions apply to the installation site.
Situation Installation
Precaution
Installation in a Control Panel
Design the control panel size, unit layout, and cooling
method so the temperature around the servo amplifier does
not exceed 55°C.
Installation Near a Heating Unit
Minimize heat radiated from the heating unit as well as any
temperature rise caused by natural convection so the
temperature around the servo amplifier does not exceed
55°C.
Installation Near a Source of Vibration
Install a vibration isolator beneath the servo amplifier to
avoid subjecting it to vibration.
Installation at a Site Exposed to
Corrosive Gas
Corrosive gas does not have an immediate effect on the
servo amplifier, but will eventually cause electronic
components and contactor-related devices to malfunction.
Take appropriate action to avoid corrosive gas.
Other Situations
Do not install the servo amplifier in hot and humid locations
or locations subject to excessive dust or iron powder in the
air.
Summary of Contents for 8U0108-E1-01
Page 4: ...iv This page intentionally left blank...
Page 6: ...vi This page intentionally left blank...
Page 12: ...XtraDrive User Manual Table of Contents Preface xii This page intentionally left blank...
Page 27: ...XtraDrive User Manual Chapter 3 Wiring 3 3 3 1 1 Single Phase 200V Main Circuit Specifications...
Page 29: ...XtraDrive User Manual Chapter 3 Wiring 3 5 3 1 3 Three phase 200V Main Circuit Specifications...
Page 30: ...XtraDrive User Manual Chapter 3 Wiring 3 6 3 1 4 Three Phase 400V Main Circuit Specifications...
Page 32: ...XtraDrive User Manual Chapter 3 Wiring 3 8 3 2 2 Three phase 1kW to 3kW 200V Models...
Page 33: ...XtraDrive User Manual Chapter 3 Wiring 3 9 3 2 3 Three phase 0 5kW to 3 0kW 400V Models...
Page 56: ...XtraDrive User Manual Chapter 3 Wiring 3 32 This page intentionally left blank...
Page 332: ......