XtraDrive User Manual
Chapter
5
: Parameter Settings and Functions
5-81
In order to set a multi-turn limit value to the encoder, perform the multi-
term limit setting operation (Fn-013).
This operation can be executed using the hand-held digital operator or
the servo amplifier panel operator.
Note:
The multi-turn limit setting is enabled only during the multi-turn limit value mismatch alarm. Cycle the
power after performing this operation.
WARNING
•
Connect the ground terminal to a class-3 ground (100
Ω
less).
Improper grounding may result in electric shock or fire.
5.7.3. Absolute
Encoder
Setup
Perform the setup operation for the absolute encoder in the following
circumstances:
•
When starting the machine for the first time.
•
When an encoder backup alarm is generated.
•
When the encoder loses power, often because of cable
disconnection.
The setup operation can be performed by using personal computer
monitor software.
The setup operation procedure shown here uses the digital operator. For
more details, refer to
Chapter 7: Using the Panel Operator.
1.
Press the
MODE/SET
key to select the Auxiliary Function mode.
2.
Press the
Up Arrow
or
Down Arrow
key to select the
parameter Fn008.
3.
Press the
DATA/SHIFT
key, holding it down for at least one
second. The following display will appear.
Summary of Contents for 8U0108-E1-01
Page 4: ...iv This page intentionally left blank...
Page 6: ...vi This page intentionally left blank...
Page 12: ...XtraDrive User Manual Table of Contents Preface xii This page intentionally left blank...
Page 27: ...XtraDrive User Manual Chapter 3 Wiring 3 3 3 1 1 Single Phase 200V Main Circuit Specifications...
Page 29: ...XtraDrive User Manual Chapter 3 Wiring 3 5 3 1 3 Three phase 200V Main Circuit Specifications...
Page 30: ...XtraDrive User Manual Chapter 3 Wiring 3 6 3 1 4 Three Phase 400V Main Circuit Specifications...
Page 32: ...XtraDrive User Manual Chapter 3 Wiring 3 8 3 2 2 Three phase 1kW to 3kW 200V Models...
Page 33: ...XtraDrive User Manual Chapter 3 Wiring 3 9 3 2 3 Three phase 0 5kW to 3 0kW 400V Models...
Page 56: ...XtraDrive User Manual Chapter 3 Wiring 3 32 This page intentionally left blank...
Page 332: ......