XtraDrive User Manual
Chapter 7: Using the Panel Operator
7-18
7.2.2. JOG
Operation
CAUTION
•
Forward Run Prohibited (/P-OT) and Reverse Run Prohibited (/N-OT) signals are not
effective during JOG operations using parameter Fn002.
Operation from the digital operator allows the servo amplifier to run the
motor. This allows checking the motor’s rotation direction and speed
setting rapidly during machine setup and testing, saving the time and
trouble of connecting to a host controller.
For the motor speed setting procedure, refer to
7.1.5 Operation in
Parameter Setting Mode
and
5.3.2 JOG Speed.
The operating procedure using the digital operator is described on the
following pages.
1.
Press the MODE/SET key to select Fn002 in the Auxiliary
Function mode.
2.
Press the DATA/SHIFT key for a minimum of one second to select
the Panel Operator Operation mode. Operation is now possible using
the panel operator.
Summary of Contents for 8U0108-E1-01
Page 4: ...iv This page intentionally left blank...
Page 6: ...vi This page intentionally left blank...
Page 12: ...XtraDrive User Manual Table of Contents Preface xii This page intentionally left blank...
Page 27: ...XtraDrive User Manual Chapter 3 Wiring 3 3 3 1 1 Single Phase 200V Main Circuit Specifications...
Page 29: ...XtraDrive User Manual Chapter 3 Wiring 3 5 3 1 3 Three phase 200V Main Circuit Specifications...
Page 30: ...XtraDrive User Manual Chapter 3 Wiring 3 6 3 1 4 Three Phase 400V Main Circuit Specifications...
Page 32: ...XtraDrive User Manual Chapter 3 Wiring 3 8 3 2 2 Three phase 1kW to 3kW 200V Models...
Page 33: ...XtraDrive User Manual Chapter 3 Wiring 3 9 3 2 3 Three phase 0 5kW to 3 0kW 400V Models...
Page 56: ...XtraDrive User Manual Chapter 3 Wiring 3 32 This page intentionally left blank...
Page 332: ......