3. SIGNALS AND WIRING
3 - 18
(2) Cable connection procedure
(a) Fabrication on cable insulator
Refer to table 3.1 and 3.2 for stripped length of cable insulator. The appropriate stripped length of
cables depends on their type, etc. Set the length considering their status.
Insulator
Core
Stripped length
Twist strands lightly and straighten them as follows.
Loose and bent strands
Twist and straighten
the strands.
You can also use a ferrule to connect with the connectors. The following shows references to select
ferrules according to wire sizes.
Ferrule model (Phoenix Contact)
Servo amplifier
Wire size
For one
For two
Crimp terminal
(Phoenix Contact)
AWG 16
AI1.5-10BK
AI-TWIN2×1.5-10BK
MR-JE-10A to
MR-JE-100A
AWG 14
AI2.5-10BU
AWG 16
AI1.5-10BK
AI-TWIN2×1.5-10BK
AWG 14
AI2.5-10BU
AI-TWIN2×2.5-10BU
MR-JE-200A to
MR-JE-300A
AWG 12
AI4-10GY
CRIMPFOX-ZA3
(b) Inserting wire
Insert the open tool as follows and push down it to open the spring. While the open tool is pushed
down, insert the stripped wire into the wire insertion hole. Check the insertion depth so that the wire
insulator does not get caught by the spring.
Release the open tool to fix the wire. Pull the wire lightly to confirm that the wire is surely connected.
The following shows a connection example of the CNP2 connector for 2 kW and 3 kW.
1) Push down the open tool.
3) Release the open tool to fix the wire.
2) Insert the wire.
Summary of Contents for MELSERVO-JE MR-JE-100A
Page 23: ...1 FUNCTIONS AND CONFIGURATION 1 12 MEMO ...
Page 29: ...2 INSTALLATION 2 6 MEMO ...
Page 91: ...3 SIGNALS AND WIRING 3 62 MEMO ...
Page 171: ...5 PARAMETERS 5 44 MEMO ...
Page 195: ...6 NORMAL GAIN ADJUSTMENT 6 24 MEMO ...
Page 221: ...7 SPECIAL ADJUSTMENT FUNCTIONS 7 26 MEMO ...
Page 249: ...8 TROUBLESHOOTING 8 28 MEMO ...
Page 255: ...9 DIMENSIONS 9 6 MEMO ...
Page 263: ...10 CHARACTERISTICS 10 8 MEMO ...
Page 293: ...11 OPTIONS AND PERIPHERAL EQUIPMENT 11 30 MEMO ...