6. NORMAL GAIN ADJUSTMENT
6 - 8
(c) Stop of one-touch tuning
During one-touch tuning, pushing the stop button stops one-touch tuning.
If the one-touch tuning is stopped, "C 0 0 0" will be displayed at status in error code.
(d) Error occurrence
If a tuning error occurs during tuning, one-touch tuning will be forcibly terminated. With that, the
following error code will be displayed in status. Check the cause of tuning error.
Table 6.2 Error code list during one-touch tuning
Error code
Name
Description
Action
C000
Tuning canceled
The stop button or "SET" of the push button
was pushed.
C001
Overshoot exceeded
The overshoot amount is lager than the value
set in [Pr. PA10 In-position range].
Increase the in-position range.
C002
Servo-off during tuning
The one-touch tuning was attempted during
servo-off.
Perform the one-touch tuning after servo-on.
C003
Control mode error
The one-touch tuning was attempted while the
torque control mode was selected in the
control modes.
Select the position control mode or speed
control mode for the control mode from the
controller, and then make one-touch tuning.
C004
Time-out
1. One cycle time during the operation has
been over 30 s.
Set the one cycle time during the operation to
30 s or less.
2. The command speed is low.
Set the servo motor speed to100 r/min or
higher.
3. The operation interval of the continuous
operation is short.
Maintain the operation interval during motor
driving about 200 ms.
C005
Load to motor inertia
ratio misestimated
1. The estimation of the load to motor inertia
ratio at one-touch tuning was a failure.
Drive the motor with meeting conditions as
follows.
Time to reach 2000 r/min is the
acceleration/deceleration time constant of 5
s or less.
Speed is 150 r/min or higher.
The load to motor inertia ratio is 100 times
or less.
The acceleration/deceleration torque is
10% or more of the rated torque.
2. The load to motor inertia ratio was not
estimated due to such as an oscillation.
Set to the auto tuning mode that does not
estimate the load to motor inertia ratio as
follows, and then execute the one-touch
tuning.
Select "Auto tuning mode 2 (_ _ _ 2)",
"Manual mode (_ _ _ 3)", or "2 gain
adjustment mode 2 (_ _ _ 4)" of "Gain
adjustment mode selection" in [Pr. PA08].
Set [Pr. PB06 Load to motor inertia ratio]
properly with manual setting.
C00F
One-touch tuning
disabled
"One-touch tuning function selection" in [Pr.
PA21] is "Disabled (_ _ _ 0)".
Select "Enabled (_ _ _ 1)".
(e) If an alarm occurs
If an alarm occurs during tuning, one-touch tuning will be forcibly terminated.
Remove the cause of the alarm and execute one-touch tuning again.
(f) If a warning occurs
If a warning which continue the motor driving occurs during the tuning, one-touch tuning will be
continued.
If a warning which does not continue the motor driving occurs during the tuning, one-touch tuning will
be stopped.
Summary of Contents for MELSERVO-JE MR-JE-100A
Page 23: ...1 FUNCTIONS AND CONFIGURATION 1 12 MEMO ...
Page 29: ...2 INSTALLATION 2 6 MEMO ...
Page 91: ...3 SIGNALS AND WIRING 3 62 MEMO ...
Page 171: ...5 PARAMETERS 5 44 MEMO ...
Page 195: ...6 NORMAL GAIN ADJUSTMENT 6 24 MEMO ...
Page 221: ...7 SPECIAL ADJUSTMENT FUNCTIONS 7 26 MEMO ...
Page 249: ...8 TROUBLESHOOTING 8 28 MEMO ...
Page 255: ...9 DIMENSIONS 9 6 MEMO ...
Page 263: ...10 CHARACTERISTICS 10 8 MEMO ...
Page 293: ...11 OPTIONS AND PERIPHERAL EQUIPMENT 11 30 MEMO ...