Chapter 1 Built-in FEnet communication
1-119
Buil
t-
in
Comm
Buil
t-
in
Problem
Corrective Measures
In case transmission
-reception is impossible
during high speed link
service
1. Check the communication speed(Auto/10/100M-TX).
It should have the same communication speed with the opposing device
to be communicated.
☞
The communication speed in the network should be same or set as
Auto for communication.
2. Check the IP address settings. The IP should be valid in the network.
☞
In case the set IP addresses are overlapped in the network or invalid
IP exists, communication is impossible.
3. Check whether the high speed link’s parameters are set.
☞
In case the parameters are not set; or the set exchange numbers are
overlapped in the network; or you have wrong block setting or block
number, communication is impossible.
4. Check the Link Enable
☞
The frame can be transmitted only when the Link Enable is set.